Office Address

400 N Ashley Dr #2600, Tampa, FL 33602

Contact Number

813-389-7871

Email Address

contact@keentelengineering.com

Substation Design in Electrical Power System

The design of a substation is a critical component of the power distribution in electrical system. The primary goal of this design is to ensure reliable and efficient power transmission and distribution to end-users.

Abstract— The design of a substation is a critical component of  the power distribution in electrical system. The primary goal of  this design is to ensure reliable and efficient power transmission  and distribution to end-users. The process of substation design  involves various electrical and mechanical components such as  transformers, switchgear, protection systems, power  transformers, and control systems. The electrical design of the  substation includes the selection of equipment, protection  schemes, and power system studies. The design must consider the  electrical load and power flow requirements, system voltage  levels, and equipment ratings. The protection systems are an  important aspect of the design, as they ensure the safety of the  equipment and the personnel, as well as the continuity of power  supply to the end-users. The mechanical design of the substation  includes the layout of the equipment, the arrangement of the  electrical and mechanical components, and the design of the  structures to support the equipment. The mechanical design must  consider the environmental conditions, seismic requirements, and  the access requirements for maintenance and inspection. The  design of a substation requires a comprehensive understanding of  the electrical power system and the equipment used in the  substation. The design must also consider the cost-effectiveness,  reliability, and maintainability of the equipment. This design  should be carried out by experienced electrical engineers who  have a deep knowledge of the electrical power system and the  equipment used in substations. 

Keywords—Substation, Busbar, Transformer, Earthing, power  system protection, batteries. 

I. INTRODUCTION 

Substation electrical design engineering is a specialized  branch of electrical engineering that deals with the design,  construction, and maintenance of electrical substations. These  substations play a critical role in the electrical power system by  transforming high-voltage electricity into low-voltage  electricity that can be safely used by homes and businesses. A  well-designed and properly functioning substation ensures a  reliable and efficient distribution of electrical power. 

Substation electrical design engineers are responsible for  creating detailed designs and specifications for the components  and systems within a substation, including transformers,  switchgear, protective relays, and control systems. They must  consider a wide range of factors, including protection,  reliability, cost-effectiveness, and environmental impact, while 

creating a substation which fulfills the exact needs of the  electrical power system it serves. 

In addition to designing new substations, substation  electrical design engineers may also be involved in upgrading  and maintaining existing substations to ensure they continue to  meet the demands of a rapidly changing electrical power  system. Whether working on new construction or upgrades,  substation electrical design engineers play a critical role in  ensuring the safe, reliable, and efficient delivery of electrical  power to communities around the world. 

After the introduction section, this paper is structured as follow in these sections: Substation/Switchyard Equipment  Selection and sizing (IEC, IS, IEEE) Standard, Substation  Layouts, ACSR Conductor Sizing, Short Circuit Calculations,  CT VT Sizing Calculations, Busbar sizing Calculations, HT &  LT Cables and Cable tray sizing calculations and voltage drop  calculations, Cable Tray Layout, Busduct sizing calculations,  Load calculations, Transformer Selection and Sizing, DG  sizing, Single Line Diagrams, Lighting Calculations,  Lightning Protections and Layouts, Earthing Calculations and  Layouts, Power System Protection and relay settings, LA  

sizing, HV circuit breakers sizing, Battery and Battery  Charger sizing Calculations, UPS sizing calculations 

II. SUBSTATION/SWITCHYARD EQUIPMENT SELECTION AND  SIZING (IEC, IS, IEEE) STANDARDS 

The selection and sizing of substation or switchyard  equipment is governed by international and national standards.  The main standards used for this purpose are: 

A. Institute of Electrical and Electronics Engineers (IEEE)  standards: 

IEEE is a professional group responsible for developing and publishing values for electrical and electronic technologies.  Some of the relevant IEEE standards for substation equipment  selection and sizing include: 

• IEEE 80 for guidelines for safe operation in AC  substation grounding 

• IEEE 141 for electric power distribution for industrial  plants 

• IEEE 1547 for linking electric power systems and  dispersed resources

B. International Electrotechnical Commission (IEC)  standards 

IEC is a global organization that creates and disseminates  regulations for technologies relevant to electrical, electronic,  and computer systems. Some of the relevant IEC standards for  substation equipment selection and sizing include: 

• IEC 62271 series for high-voltage switchgear and  control gear 

• IEC 61850 for communication and control in  substations 

• IEC 60038 for standard voltages 

• IEC 60354 for high-voltage bushings 

C. Indian Standards (IS) standard 

The national standardization body for India is called the  Bureau of Indian Standards (BIS), which develops and  publishes Indian Standards (IS) for various industries,  including the electrical sector. Some of the relevant IS  standards for substation equipment selection and sizing  include: 

• IS 1180 for high-voltage switchgear and control gear • IS 732 for earthing of electrical installations. • IS 8186 for high voltage bushings. 

These standards provide guidelines for the selection and  sizing of equipment, as well as specifications for their design,  testing, and performance. They help ensure that substations are  designed, built and operated in a safe and reliable manner, and  promote interoperability and compatibility between different  equipment and systems. 

III. SUBSTATION LAYOUTS 

A substation layout is the arrangement of various electrical  equipment and components within a substation. The layout is  designed to ensure safe and efficient operation of the substation  and to meet the specific requirements of the electrical power system it serves. 

Typically, a substation layout consists of the following  components: 

1. Power transformers – used to step up or step down the  voltage of incoming electrical power. 

2. Switchgear – used to control, protect, and isolate  electrical equipment within the substation. 

3. Busbars – conductors that transfer electrical power  within the substation. 

4. Circuit breakers – used to interrupt the flow of  electrical current in case of a fault. 

5. Protective relays – used to detect faults and trip the  circuit breaker to isolate the faulted equipment. 

6. Control panels – used to control and monitor the  operation of the substation. 

7. Instrument transformers – used to measure electrical  quantities such as voltage, current, and power. 

8. Lightning arresters – used to protect the substation  equipment from lightning strikes. 

9. Grounding system – used to ensure a safe path for electrical current in case of a fault. 

The specific layout of a substation depends on the voltage  levels, power capacity, and specific requirements of the  electrical power system it serves. The layout must also comply  with relevant electrical safety standards and regulations 

IV. ACSR CONDUCTOR SIZING 

ACSR (Aluminum Conductor Steel Reinforced) is a type of  electrical conductor used in overhead transmission and  distribution systems. It is a composite material consisting of an  aluminum core surrounded by one or more steel wires. ACSR  conductors are used in a variety of applications including  substation power transmission and distribution. 

The sizing of ACSR conductors in a substation is an  important aspect of ensuring efficient and reliable power  transmission. The size of the conductor determines its ability to  carry electrical current without overheating and causing  damage to the surrounding equipment. In this blog, we will  explore the factors that need to be considered when selecting  the appropriate size of ACSR conductor for a substation. 

1. Load Requirements: One of the primary  considerations when selecting the size of ACSR  conductor is the amount of electrical current that it will need to carry. The size of the conductor should  be selected based on the load requirements of the  substation, which will depend on the number of  customers, the type of equipment being used, and  other factors. 

2. Voltage Level: Another important factor to consider  when sizing ACSR conductors is the voltage level of  the substation. High voltage systems require larger  conductors than low voltage systems, so it is  important to take into account the voltage level when  making a selection. 

3. Distance of Transmission: The distance of  transmission is another important factor to consider  when selecting the size of ACSR conductor.  Conductors that are used over longer distances will  require a larger cross-sectional area to reduce  resistance and minimize energy loss. 

4. Ambient Temperature: The ambient temperature of  the environment in which the ACSR conductor will  be used is another important factor to consider.  Conductors used in hot environments will require a  larger cross-sectional area to prevent overheating and  ensure efficient power transmission. 

5. Safety Factors: Finally, it is important to take into  account safety factors when selecting the size of  ACSR conductor. Conductors should be selected  based on their ability to carry electrical current  without overheating and causing damage to the  surrounding equipment. This will depend on the  specific requirements of the substation, and the safety  factors should be determined by a licensed electrical  engineer. 

In conclusion, ACSR conductors play a critical role in  ensuring efficient and reliable power transmission in  substations. The size of the conductor should be selected based 

on the load requirements, voltage level, distance of  transmission, ambient temperature, and safety factors. By  considering these factors and working with a licensed electrical  engineer, you can ensure that the ACSR conductor selected for  your substation will meet your specific needs and provide  reliable power transmission for years to come. 

V. SHORT CIRCUIT CALCULATIONS DURING SUBSTATION DESIGN 

Short circuit calculations are an important aspect of  substation design, as they help to determine the maximum fault  current that a substation can handle and ensure the safety of the  equipment and personnel. Short circuit calculations are used to  size the protective devices, such as circuit breakers and fuses,  and to determine the necessary equipment ratings to ensure  safe and reliable operation of the substation. Here are the steps  involved in performing short circuit calculations during  substation design: 

1. Determine the system voltage: The first step in  performing short circuit calculations is to determine  the system voltage. This will determine the maximum  fault current that the system can handle and will be  used in subsequent calculations. 

2. Determine the short circuit current that is available:  The maximum fault is the available short circuit  current that can flow in the system. This can be  determined using the formula I = V / Z, where V is  the system voltage and the system’s impedance is Z.  The impedance of the system can be determined by  analyzing the network and taking into account the  resistance, inductance, and capacitance of the  conductors and other components. 

3. Determine the protective device ratings: Once the  available short circuit current has been determined,  the protective device ratings can be calculated. The  protective device rating is the maximum current that  the device can handle without damaging itself or the  equipment it is protecting. This will vary based on  the substation’s unique needs, such as the size of the  wires and the equipment in use. 

4. Consider the time-current characteristics of the protective devices: The time-current characteristics of  the protective devices must also be taken into account  when performing short circuit calculations. This  refers to the time it takes for the protective device to  operate and clear a fault, and is an important factor in  ensuring the safety of the equipment and personnel. 

5. Evaluate the equipment withstand capability: Finally,  it is important to evaluate the withstand capability of  the equipment in the substation. This involves  determining the maximum fault current that the  equipment can handle without damage, and ensuring  that the protective devices are rated accordingly. 

In conclusion, short circuit calculations are a critical aspect  of substation design, as they help to ensure the safety and  reliability of the equipment and personnel. By performing  accurate short circuit calculations, substation designers can  

determine the necessary equipment ratings and protective  device ratings, and ensure that the substation is designed to  meet the specific requirements of the application. 

VI. CURRENT TRANSFORMER AND VOLTAGE  

TRANSFORMER SIZING CALCULATIONS  

When designing a substation, it is important to accurately  size the current transformers (CTs) and voltage transformers  (VTs) to ensure the proper operation of the protection and  measurement equipment. Here are the general steps for sizing  CTs and VTs: 

A. Current Transformers: 

1. Determine the maximum current that will flow in the  protected circuit. This is typically the highest short circuit current that can exist in the system. 

2. Select the CT rating that is appropriate for the  maximum current. CTs are typically rated in terms of  their secondary current, and the most common ratings  are 5A or 1A. 

3. Determine the accuracy class required for the CT.  The accuracy class specifies the maximum error  between the primary current and the secondary  current. Common accuracy classes are 0.5, 0.2, and  0.1. 

4. Calculate the burden (load) on the CT secondary. The  burden is the total impedance of the connected  protection and measurement equipment. 

5. Check the CT’s knee point voltage to ensure it is  suitable for the burden. The knee point voltage is the  voltage that appears across the CT’s secondary  winding when the primary current is equal to the  CT’s rated primary current. 

B. Voltage Transformers: 

1. Determine the voltage levels in the system, including  the maximum and minimum operating voltages and  the maximum transient overvoltages. 

2. Select the VT rating that is appropriate for the  voltage levels. VTs are typically rated in terms of  their secondary voltage, and the most common  ratings are 110V or 120V. 

3. Determine the accuracy class required for the VT.  The accuracy class specifies the maximum error  between the primary voltage and the secondary  voltage. Common accuracy classes are 0.5, 0.2, and  0.1. 

4. Calculate the burden (load) on the VT secondary. The  burden is the total impedance of the connected  protection and measurement equipment. 

5. Check the VT’s insulation level to ensure it is suitable  for the voltage levels and burden. 

Note that these are general steps and the exact sizing  calculations will depend on the specific system and equipment  being used. It is always recommended to consult the  manufacturer’s technical specifications and guidelines for the  specific CTs and VTs being used.

VII. BUSBAR SIZING CALCULATIONS 

Busbar sizing is an important aspect of substation design as  it affects the electrical performance and stability of the system.  The following are the general steps for busbar sizing  calculations: 

1. Determine the maximum current that will flow  through the busbar. This is typically the highest  short-circuit current that can exist in the system. 

2. Choose the appropriate material for the busbar.  Copper and aluminum are the most commonly used  materials for busbars, but the choice will depend on  factors such as cost, conductivity, and thermal  conductivity. 

3. Determine the required cross-sectional area of the  busbar based on the maximum current and the chosen  material. The cross-sectional area determines the  ampacity of the busbar, which is the maximum  current it can carry without overheating. 

4. Consider the operating temperature and ambient  temperature. The busbar must be able to operate  within its temperature limits, and the ambient  temperature must be taken into account when  calculating the ampacity. 

5. Check the voltage drop across the busbar. The  voltage drop should be within acceptable limits,  typically 3% or less, to ensure proper operation of the  equipment connected to the busbar. 

6. Consider the busbar’s mechanical and thermal  stability. The busbar must be able to withstand the  mechanical and thermal stresses caused by the  current and temperature changes. 

Note that these are general steps and the exact sizing  calculations will depend on the specific system and equipment  being used. It is always recommended to consult the  manufacturer’s technical specifications and guidelines for the  specific busbar material and installation requirements. 

VIII. HT & LT CABLES AND CABLE TRAY SIZING  CALCULATIONS AND VOLTAGE DROP CALCULATIONS 

The sizing of high tension (HT) and low tension (LT)  cables, as well as cable trays, is an important aspect of  electrical design and engineering. The size of the cable and tray  is determined by several factors, including the current carrying  capacity, the voltage drop, and the temperature increase in the  cable. 

A cable’s current carrying capacity is the highest amount of  current that it can safely carry without overheating. This  capacity is determined by the conductor’s cross-sectional area,  conductor material, and insulation type. 

Voltage drop is the amount of voltage that is lost along the  length of a cable as a result of resistance of the conductor. The  drop in voltage is important because it affects the efficiency of  the electrical system and can lead to problems such as  equipment failure or reduced power output. The voltage drop is  calculated using the formula: 

Voltage drop = (2 * resistance * current) / 1000 

where resistance is the resistance of the conductor in ohms  per kilometer and current is the current flowing through the  cable in amperes. 

The temperature rise of a cable is the increase in  temperature of the cable due to the flow of current. The  temperature rise is important because it affects the durability  and safety of the cable. The temperature rise is calculated using  the formula: 

Temperature rise = (current^2 * resistance) / (conductivity  * cross-sectional area) 

where conductivity is the conductivity of the conductor in  Siemens per meter and cross-sectional area is the conductor’s  cross-sectional area in square millimeters. 

Cable tray sizing is determined by the total cross-sectional  area of the cables that will be placed in the tray, as well as the  type of cable tray being used (perforated, solid bottom, etc.).  The cable tray must be large enough to accommodate the  cables and allow for proper air circulation to dissipate heat. 

In conclusion, the sizing of HT and LT cables and cable  trays involves a consideration of several important factors,  including current carrying capacity, voltage drop, and  temperature rise. The calculations and considerations involved  in sizing these components are crucial for ensuring the safe and  efficient operation of an electrical system. 

IX. CABLE TRAY LAYOUT 

Cable tray layout in a substation is the arrangement of cable  trays and their components, such as supports and conduit  connections, that provide a means to support and protect  electrical power cables within the substation. The layout is an  important aspect of substation design as it affects the  accessibility, maintenance, and safety of the electrical cables. 

Here are some general guidelines for cable tray layout in a  substation: 

1. Cable tray routing: Cable trays should be routed in a  manner that minimizes the length of cable runs,  reduces the number of bends, and provides easy  access for maintenance and inspection. 

2. Cable tray supports: Cable trays should be supported  at regular intervals to ensure stability and to prevent  sagging. Supports should be designed to withstand  the weight of the cables and any additional loads,  such as wind or seismic forces. 

3. Cable tray height: Cable trays should be installed at a  height that allows sufficient clearance for  maintenance and inspection, while also reducing the  risk of damage from equipment and vehicles. 

4. Cable tray separation: Cable trays should be  separated from each other and from other equipment  to prevent interference and to ensure adequate  ventilation. 

5. Conduit connections: Cable trays should be  connected to conduit systems to provide a transition  from overhead to underground cable runs and to  provide additional protection for the cables. 

6. Cable tray material: Cable trays should be made of a  material that is durable, corrosion-resistant, and 

suitable for the operating environment of the  substation. 

7. Cable tray labeling: Cable trays should be labeled to  identify the type of cables they contain and their  routing, which is important for maintenance and  emergency response. 

These guidelines are intended to provide a general  overview of cable tray layout in substations. It is important to  consult with electrical engineers and industry standards, such  as the “National Electrical Code” (NEC) and the “International  Electrotechnical Commission” (IEC), for more specific  requirements and recommendations 

X. BUSDUCT SIZING CALCULATIONS 

Bus duct sizing calculations are an important aspect of  substation design engineering, as it determines the capacity of  the bus duct system to safely and efficiently transmit electrical  power. The following steps can be followed to size a bus duct  system: 

1. Determine the load demand: The first step is to  determine the load demand, which is the total amount  of electrical power that will be transmitted through  the bus duct system. 

2. Select the voltage level: The next step is to select the  voltage level for the bus duct system, which is  usually either 11 kV or 33 kV. 

3. Determine the short-circuit current: The short-circuit  current is a crucial factor in determining the size of  bus ducts because it establishes the maximum current  that may pass through the system in the event of a  short circuit. The short-circuit current can be  calculated using industry standard methods such as  the symmetrical component method. 

4. Select the conductor material: The conductor material  should have a high conductivity and high thermal  capacity, with aluminum and copper being the most  commonly used materials. 

5. Determine the conductor size: The conductor size is  determined based on the load demand, voltage level,  and short-circuit current, as well as the conductor  material and the operating temperature of the bus  duct system. 

6. Select the bus duct configuration: The bus duct  configuration can be either single-phase or three phase, and can be either segregated or integral. 

7. Determine the bus duct cross-sectional area: The  cross-sectional area of the bus duct is determined  based on the conductor size, number of conductors,  and the bus duct configuration. 

8. Consider the bus duct insulation: The bus duct  insulation should be designed to withstand the  electrical and thermal stresses of the bus duct system,  and to provide adequate electrical insulation between  the conductors. 

9. Consider the bus duct cooling: The bus duct cooling  system should be designed to prevent overheating of  

the conductors and the insulation, and to ensure safe  and efficient operation of the bus duct system. 

It’s important to follow industry standards and guidelines  when performing bus duct sizing calculations, such as the  IEEE Std 80-2013, to ensure safe and reliable operation of the  bus duct system. 

XI. LOAD CALCULATIONS 

Load calculations are an important aspect of substation  design engineering as they help determine the electrical  demand of a substation and the equipment required to meet that  demand. The calculations take into account various factors such as the type of load, the load density, the load duration, and  the diversity factor of the load. 

To perform load calculations in substation design  engineering, the following steps can be followed: 1. Determine the type of load: There are two types of  loads in a substation – continuous and non continuous. Continuous loads are those that are  always present, like lighting and air conditioning  systems, while non-continuous loads are those that  are not always present, like motors and transformers. 2. Determine the load density: This is the amount of  electrical power required per unit area. It is calculated  by dividing the total power demand by the area of the  substation. 

3. Determine the load duration: This is the amount of  time that the load is present. It is important to  consider the load duration as it affects the size of the  equipment required to meet the load demand. 

4. Determine the diversity factor of the load: This is the  ratio of a substation’s maximum demand to the  aggregate of each load’s unique maximum needs. It  takes into account the fact that not all loads will be  present at the same time. 

5. Calculate the load demand: The load demand is  calculated by multiplying the load density by the area  of the substation and then by the diversity factor. 

6. Select the equipment: Based on the load demand  calculation, the appropriate equipment such as  transformers, switchgear, and circuit breakers can be  selected to meet the electrical demand of the  substation. 

It is important to note that load calculations should be  reviewed and updated regularly to ensure that the substation is  equipped to handle changing electrical demands 

XII. TRANSFORMER SELECTION AND SIZING 

Transformer selection and sizing is a crucial step in the  design of a substation. The right transformer size and type must  be selected to meet the electrical requirements of the system  and ensure safe, efficient, and reliable operation. The following  are some of the key considerations in transformer selection and  sizing: 

1. Load requirements: The transformer’s size must  correspond to the system’s highest anticipated load  demand. The load demand should be estimated based 

on the connected equipment and their power  requirements. 

2. Voltage levels: The system’s voltage levels should be  taken into account when selecting the transformer.  Transformers are typically designed to change the  voltage, either up or down in the system. 

3. Efficiency: The efficiency of the transformer should  be considered when selecting and sizing the  transformer. High-efficiency transformers can help  reduce energy losses and lower operating costs. 

4. Short-circuit capacity: The transformer should be  able to tolerate any potential short-circuit currents in  the system. The short-circuit capacity of the  transformer should be calculated based on the  expected short-circuit currents in the system. 

5. Environmental conditions: The environmental  conditions of the substation site should be taken into account when selecting the transformer. This includes  temperature, humidity, altitude, and exposure to  corrosive elements. 

6. Safety considerations: The safety of the transformer  should be considered during the selection and sizing  process. Transformers should meet relevant safety  standards and certifications. 

In summary, the selection and sizing of transformers in  substation design is a complex process that requires careful  consideration of various electrical, operational, and  environmental factors. An experienced electrical engineer with  knowledge of the specific requirements of the substation  should be consulted to ensure the right transformer is selected  and sized for the system. 

XIII. DG SIZING 

DG (Distributed Generation) Sizing for a Substation Design  refers to the process of determining the size and capacity of a  distributed generation system that needs to be installed in a  substation to meet the energy needs of a specific location or  distribution network. 

The following are the key factors that need to be considered  when sizing a DG system for a substation design: 1. Energy demand: The first step is to determine the  energy demand at the substation. This information  can be obtained from energy consumption data for  the area or by estimating the future energy demand  based on growth projections. 

2. Access to renewable energy sources: The next step is  to assess the availability of renewable energy sources  such as solar, wind, or hydro power at the substation  location. 

3. System efficiency: The efficiency of the DG system,  including the conversion efficiency of the generators  and the efficiency of the power electronics, must be  taken into account when sizing the system. 

4. Power quality requirements: The power quality  requirements, such as voltage and frequency stability,  must be considered when sizing the DG system. 

5. Grid connection requirements: The requirements for  connecting the DG system to the grid, including the  voltage and frequency range, must be taken into  account when sizing the system. 

6. Cost considerations: The cost of the DG system,  including the initial investment and operating costs,  must be considered when sizing the system. 

Once all of these factors have been taken into account, the  size and capacity of the DG system can be determined, and the  substation design can be finalized. It is important to note that  the DG sizing for a substation design is a complex process that  requires a comprehensive understanding of the energy system,  the available technology, and the economic and regulatory  factors that impact the deployment of DG systems. 

XIV. SINGLE LINE DIAGRAMS 

A single line diagram (SLD) is a simplified representation  of a substation, showing the main components and their  connections. It is typically used during the design phase of a  substation to provide a clear knowledge of the electrical  equipment and their relationships. 

The single line diagram will typically include the following  components: 

1. Power transformers: These are utilized to increase or  decrease the voltage of the incoming power. 

2. Busbars: The conductors that connect the  transformers, generators, and other electrical  equipment in the substation. 

3. Circuit breakers: Devices used to interrupt the flow of current in the event of an electrical fault. 

4. Isolators: Devices for isolating certain areas of the  substation so they may be maintained or repaired. 5. Protective relays: Devices used to detect faults and  

trip the circuit breaker to isolate the faulted section. 6. Metering equipment: Devices used to measure the  electrical parameters of the incoming and outgoing  power. 

7. Grounding system: A network of conductors used to  give fault current a low-impedance route to the earth. The single line diagram should also show the  electrical connections between the components and  the power flow direction. The diagram should be  clear and easy to understand, with annotations and  labels to explain the various components and their  functions. 

XV. LIGHTING CALCULATIONS 

Lighting calculations are an important aspect of substation  design as they ensure that the substation is well-lit, safe, and  meets local regulations. The following steps are involved in  lighting calculations during a substation design project: 

1. Determine the lighting requirements: This involves  determining the light level (in lux or foot-candles)  required for various areas within the substation such  as the control room, switchyard, and other outdoor  areas. The light level requirements are usually  specified in local regulations or industry standards.

2. Determine the light sources: The next step is to  determine the type of light sources to be used in the  substation, such as LED lights, fluorescent lights, or  high-intensity discharge (HID) lights. The choice of  light source will depend on various factors such as  cost, energy efficiency, and durability. 

3. Calculate the number of light fixtures: The number of  light fixtures required for each area can be calculated  using the formula: Number of fixtures = Total light  output required / Light output per fixture 

4. Determine the light distribution: The light  distribution pattern of the fixtures should be chosen  to ensure uniform lighting and minimize shadows.  This can be achieved by using fixtures with specific  light distribution patterns or by using diffusers. 

5. Perform a lighting simulation: A lighting simulation  can be performed to verify that the proposed lighting  design meets the required light levels. The simulation  can also be used to identify any areas that may  require additional lighting. 

6. Review and revise the design: The lighting design  should be reviewed and revised as necessary to  ensure that it meets the required light levels, is  energy-efficient, and complies with local regulations. 

In summary, lighting calculations during a substation  design project involve determining the lighting requirements,  selecting the light sources, calculating the number of light  fixtures, determining the light distribution, performing a  lighting simulation, and reviewing and revising the design as  necessary. 

XVI. LIGHTNING PROTECTIONS AND LAYOUTS 

Lightning protection is an important aspect of substation  design engineering as it helps to prevent damage to equipment  and ensure the safety of personnel working in the substation.  There are several methods for protecting a substation from lightning strikes, including the use of lightning rods, air  terminals, down conductors, and earthing systems. 

The layout of a substation is also important for lightning  protection. The substation should be designed in such a way  that there is a clear path for lightning to follow to the earth,  minimizing the risk of damage to equipment and ensuring the 

safety of personnel. This can be achieved by ensuring that all  tall structures, such as transmission towers and buildings, are  equipped with air terminals, down conductors, and earthing  systems. The earthing system should be designed to provide a  low impedance path for lightning to follow to the earth,  reducing the risk of damage to equipment and ensuring the  safety of personnel. 

It is also important to consider the layout of the substation  with respect to surrounding structures and landscapes. For  example, substations should be located away from large trees  and other tall structures that could attract lightning strikes.  Additionally, substations should be positioned on high ground  to reduce the risk of flooding, which could compromise the  effectiveness of the earthing system. 

In conclusion, substation design engineers should give  careful consideration to lightning protection and layout when designing a new substation. By implementing effective  lightning protection measures and designing the substation  layout in a way that minimizes the risk of damage to equipment  and ensures the safety of personnel, engineers can help to  ensure that the substation operates reliably and safely. 

XVII. EARTHING CALCULATIONS AND LAYOUTS 

Earthing is a critical aspect of substation design engineering  as it ensures the safety of the equipment, personnel, and the  public. The earthing system provides a low-resistance path to  the ground for fault currents, which helps to limit the potential  of electrical shock and equipment damage. 

There are several steps involved in earthing calculations  and layouts for a substation design: 

1. Determining the earthing grid size: The size of the earthing grid is dependent upon the fault current level and the type of soil at the substation site. To measure  soil resistance, a soil resistivity test is conducted,  which is then used to calculate the size of the  earthing grid. 

2. Earthing electrode selection: The type of earthing  electrode to be used in the substation depends on the  soil resistivity and the fault current level. Common  types of earthing electrodes include copper-bonded  steel rods, ground plates, and earth mats. 

3. Earthing grid layout: The earthing grid layout is  designed based on the earthing grid size and  electrode selection. The earthing grid should be  designed to provide a low-resistance path to ground  and to ensure that the fault current is distributed  evenly over the grid. 

4. Earthing conductor sizing: The size of the earthing  conductor depends on the fault current level, the  earthing electrode size, and the earthing grid layout.  The earthing conductor should be sized to ensure that  it can safely carry the fault current without  overheating or melting. 

5. Bonding and earthing connections: All metallic parts  of the substation equipment should be bonded  together and connected to the earthing grid to ensure  that they are at the same potential. This helps to  prevent electrical shock and equipment damage. 

6. Earthing resistance testing: The earthing system  should be tested after installation to ensure that it has  a low resistance to ground. This can be done using a  fall-of-potential test or a four-wire resistance test. 

In conclusion, earthing calculations and layouts are crucial  for the safe and reliable operation of a substation. Proper  earthing design and installation are essential to guarantee the  public’s, employees’, and equipment’s safety. 

XVIII. POWER SYSTEM PROTECTION AND RELAY SETTINGS 

Power system protection is a critical component of  substation design and operation. It involves the use of relays,  circuit breakers, and other protective devices to detect and 

isolate faults within the electrical power system. This helps to  minimize damage and prevent widespread power outages. Relay settings are critical in determining the performance  of protection systems. They control the operating  characteristics of the relays and determine the conditions under  which they will trip, or disconnect, the faulty section of the electrical system. 

The following are some of the important aspects to consider  when setting up the protection and control systems in a  substation: 

1. Zone of protection: The zone of protection refers to  the part of the electrical system that is monitored and protected by a particular relay. It is important to  ensure that the relay settings are appropriate for the  specific zone of protection in order to ensure that the  relay operates as intended. 

2. Time delay: Time delay is the amount of time that a  relay takes to trip after it has detected a fault. The  time delay is important in order to allow the relay to  differentiate between temporary and permanent  faults. 

3. Current settings: The current setting of a relay  determines the level of current that has to be met for  the relay to trip. This setting should be appropriate  for the type of fault that is expected to occur in the  zone of protection. 

4. Voltage settings: The voltage setting of a relay  determines the level of voltage that has to be met for  the relay to trip.. This setting should be appropriate  for the type of fault that is expected to occur in the  zone of protection. 

5. Coordination: Relays must be properly coordinated to  ensure that they operate in the correct sequence during a fault. This helps to minimize the extent of  the fault and prevent widespread power outages. 

In conclusion, power system protection and relay settings contribute significantly to maintaining the safe and reliable  functioning of substations. It is crucial to properly take into  account the specific requirements of each substation and to set  the protection and control systems accordingly. 

XIX. LIGHTNING ARRESTER SIZING 

A lightning arrester (LA) is an electrical safety device  designed to protect electrical equipment, such as substations,  from damage due to lightning strikes. Here is a general  overview of the design of a lightning arrester in a substation: 

6. Installation: LAs are typically installed at the highest  point of the substation, such as on the roof or on top  of a tall structure. This allows them to be in close  proximity to the lightning strikes and intercept them  before they reach the electrical equipment. 

7. Protection Zones: A substation is divided into  different protection zones, each of which requires a  different level of protection from lightning. LAs are  installed in each of these zones to provide an  appropriate level of protection. 

8. Surge Diverter: The LA contains a surge diverter,  which is a device that diverts the lightning current  away from the electrical equipment. This is usually  achieved through the use of a spark gap or a metal  oxide varistor (MOV). 

9. Grounding: The LA is connected to a grounding  system that creates a low-impedance conduit for  lightning current to go through on its way to earth.  This helps to reduce the voltage that the electrical  equipment is exposed to during a lightning strike. 

10. Monitoring and Testing: LAs should be regularly  tested and monitored to ensure that they are  functioning properly. This can be done through the  use of surge generators, which simulate lightning  strikes and test the performance of the LA. 

In conclusion, the design of a lightning arrester in a  substation involves the installation of the LA at the highest  point, the division of the substation into different protection  zones, the use of a surge diverter, the connection to a  grounding system, and regular monitoring and testing. 

XX. HV CIRCUIT BREAKERS SIZING 

High voltage (HV) circuit breakers play a critical role in the  protection and control of electrical power systems. The sizing  of HV circuit breakers in substation design is an important  aspect to guarantee the power system’s dependable and secure  functioning. The following factors need to be considered when  sizing HV circuit breakers: 

1. Maximum continuous current: This is the maximum  current that the breaker is capable of carrying  continuously without any damage to the breaker or  the electrical system. 

2. Maximum short-circuit current: This is the greatest  current that may pass through the breaker during a  short-circuit event. The breaker must be able to interrupt the short-circuit current within a specified  time. 

3. Voltage level: The breaker must be rated for the  operating voltage of the electrical system. 

4. System configuration: The breaker must be selected  based on the configuration of the electrical system,  including the type of power transformers, generators,  and other equipment connected to the breaker. 

5. Short-circuit protection coordination: The breaker  must be selected to coordinate with other protective  devices in the electrical system, such as fuses,  reclosers, and protective relays, to ensure that the  breaker operates within the specified time during a  fault. 

6. Breaking capacity: The breaker must have sufficient  breaking capacity to safely interrupt the maximum  short-circuit current. 

7. Operating mechanism: The breaker must have an  operating mechanism that is reliable and capable of  operating under the conditions of the electrical  system.

In conclusion, the sizing of HV circuit breakers in  substation design requires careful consideration of several  technical and operational factors to guarantee the power  system’s dependable and secure functioning. 

XXI. BATTERY AND BATTERY CHARGER SIZING  CALCULATIONS 

In a substation design, the sizing of the battery and battery  charger is an important aspect to consider ensuring proper  operation of the backup power system. The following are the  steps involved in calculating the size of the battery and battery  charger: 

1. Determine the load requirements: The first step is to  determine the load requirements, which includes the  total power requirement of the equipment in the  substation that needs to be powered by the backup  system in the event of a power failure. 

2. Calculate the battery capacity: The next step is to  calculate the battery capacity, which is the amount of  energy stored in the battery. This is calculated based  on the load requirements, the discharge time required,  and the discharge rate of the battery. 

3. Determine the battery voltage: The voltage of the  battery is measured depending on the voltage needs of the equipment in the substation. 

4. Calculate the battery current: The battery current is  calculated by dividing the battery capacity by the  battery voltage. 

5. Determine the battery charger size: The size of the  battery charger is determined based on the battery  current and the charging time required to fully charge  the battery. 

6. Calculate the battery charger voltage: The voltage of  the battery charger is measured depending on the  voltage demand of the battery. 

7. Calculate the battery charger current: The battery  charger current is calculated by dividing the battery  capacity by the charging time required and the  battery charger voltage. 

8. Select the battery and battery charger: Based on the  calculations, a suitable battery and battery charger are  selected from the available options in the market. 

It is important to note that the calculations need to be done  carefully to ensure that the battery and battery charger are  appropriately sized for the substation requirements. A battery  and battery charger that is undersized may not provide  sufficient backup power during an outage, while an oversized  battery and battery charger may result in unnecessary costs 

XXII. UPS SIZING CALCULATIONS 

UPS (Uninterruptible Power Supply) sizing during  substation design engineering involves determining the amount  of power required to keep the substation’s critical loads running  in the event of a power outage. The calculation involves  several factors, including: 

1. Load Capacity: The first step is to determine the total  load capacity of all the critical loads that the UPS  

needs to support. This includes all electrical  equipment such as transformers, switchgear, and  control systems. 

2. Power Consumption: The next step is to determine  the power consumption of each critical load. This  includes both the active power (measured in  kilowatts) and the reactive power (measured in  kilovars). 

3. Operating Time: The next step is to determine the  operating time of the UPS. This is the time required  to keep the critical loads running in the event of a  power outage. A typical operating time is between 10  minutes and 4 hours. 

4. Battery Capacity: The next step is to determine the  battery capacity required to support the critical loads  during the operating time. This is calculated based on  the total load capacity and the operating time. 

5. Inverter Capacity: The final step is to determine the  inverter capacity needed for converting DC power to  AC power from the battery to supply the critical  loads. This is calculated based on the total load  capacity and the operating time. 

It’s important to note that UPS sizing calculations should be  done by a qualified electrical engineer with experience in  power system design. The calculations should take into account  the specific requirements of the substation, including the  location, environment, and local electrical codes and standards. 

REFERENCES 

[1] M. Kezunovic, Y. Guan, C. Guo, and M. Ghavami, “The  21st century substation design: Vision of the future,” in 2010  IREP Symposium Bulk Power System Dynamics and Control – VIII (IREP), Aug. 2010, pp. 1–8. doi:  10.1109/IREP.2010.5563267. 

[2] J. D. McDonald, Ed., Electric Power Substations  Engineering, 1st ed. CRC Press, 2003. doi:  10.1201/9780203486498. 

[3] D. Atanackovic, D. T. McGillis, and F. D. Galiana, “The  application of multi-criteria analysis to substation design,”  IEEE Transactions on Power Systems, vol. 13, no. 3, pp.  1172–1178, Aug. 1998, doi: 10.1109/59.709116. 

[4] L. Zhao, I. Brandao Machado Matsuo, Y. Zhou, and W.-J.  Lee, “Design of an Industrial IoT-Based Monitoring System  for Power Substations,” IEEE Transactions on Industry  Applications, vol. 55, no. 6, pp. 5666–5674, Nov. 2019, doi:  10.1109/TIA.2019.2940668. 

[5] M. Kezunovic and G. Latisko, “Automated monitoring  functions for improved power system operation and control,”  in IEEE Power Engineering Society General Meeting, 2005,  Jun. 2005, pp. 2708-2711 Vol. 3. doi:  10.1109/PES.2005.1489699. 

[6] Q. B. Dam, A. P. S. Meliopoulos, G. T. Heydt, and A.  Bose, “A Breaker-Oriented, Three-Phase IEEE 24-Substation  Test System,” IEEE Transactions on Power Systems, vol. 25, 

Let’s Connect

Fill in the form below with the relevant information, and we’ll connect with you ASAP to discuss your project requirements.

Learn More
Engineering staff is taking notes - Image - Keentel Engineering