Part A — 87T and Restricted Ground Fault Protection at a Glance
Almost every medium and large power transformer in North America is protected by a percentage-restrained differential relay, device 87T. It is fast, selective, and for most internal faults it is the protection that does the work. That success creates a common assumption: if a transformer has 87T, its windings are covered.
For a large class of transformers, that assumption is wrong. On a delta–wye transformer whose wye winding is grounded through a neutral grounding resistor (NGR), a ground fault inside the wye winding can produce a differential current far below the 87T minimum pickup — not because the relay is badly set, but because of the physics of a resistance-grounded winding and the way a transformer differential relay must treat zero-sequence current. On a typical 5 MVA, 34.5–4.16 kV unit with a 400 A resistor, Keentel's worked example in this guide shows that a differential relay set at a common minimum pickup of 0.3 per unit cannot see a ground fault anywhere in roughly the lower 95% of the wye winding. Restricted ground fault protection — called restricted earth fault (REF) internationally and usually designated 87N or 87G in US practice — closes most of that gap, typically detecting faults down to within 5–10% of the neutral.
That is why well-designed transformer protection schemes use both. They are not duplicates. Each one protects a part of the transformer the other cannot reach.
This guide is Keentel Engineering's complete technical treatment of the subject. It explains how 87T and 87N work, why each has blind spots, how to calculate exactly how much of a winding each element covers, how to specify current transformers (CTs) for both, how to set high-impedance and low-impedance restricted ground fault elements, and how to commission and maintain the scheme under NERC PRC-005-6 where the transformer is part of the Bulk Electric System. Every number is worked through on US voltage classes — 4.16, 13.8, 34.5, 69, 115 and 138 kV — and US device numbers, standards and terminology.
Keentel's position. Keentel Engineering is an independent power engineering firm. We develop and peer-review protective relay settings, perform short-circuit and CT studies, design substations and grounding systems, witness commissioning and analyze relay events for utilities, industrial plants, data centers and solar, wind and battery energy storage (BESS) facilities from 4 kV to 765 kV. We do not sell relays or test equipment; our only interest is that your transformer is protected and that the evidence proves it.
Who this guide is for
- Protection engineers setting or reviewing transformer differential and ground differential elements.
- Substation and electrical design engineers specifying CTs, neutral grounding resistors and relay panels.
- Data center, industrial and campus electrical owners whose 13.8 kV and 4.16 kV systems are low-resistance grounded.
- Solar, wind and BESS owners and EPC contractors responsible for main power transformers and collector-system grounding.
- Utility asset and compliance managers responsible for PRC-005-6 maintenance, PRC-004 misoperation analysis and PRC-027-1 coordination.
- Commissioning and testing engineers who need to prove polarity, stability and sensitivity before energization.
Key facts at a glance
| Item | Value or practice | Basis |
|---|---|---|
| US device number for transformer differential | 87T (often written 87 with a "T" suffix) | IEEE C37.2 device function numbers |
| US designation for restricted ground fault | 87N, 87G or 87GD (ground differential); "64" is used internationally | IEEE C37.2; industry practice |
| Meaning of device 64 in IEEE C37.2 | Ground detector relay (commonly generator stator or field ground) | IEEE C37.2 |
| Standard ANSI angular displacement, delta–wye | Low-voltage side lags high-voltage side by 30° | IEEE C57.12.00 |
| Typical low-resistance grounding current, 4.16–34.5 kV | 200–1,000 A, often 400 A, rated 10 s | IEEE C57.32, IEEE 142 practice |
| Resistance for 400 A at 4.16 kV / 13.8 kV | 6.00 Ω / 19.92 Ω | R = V_LN / I_NGR (Keentel calculation) |
| Typical numerical 87T minimum pickup | 0.2–0.5 per unit of tap (0.3 common) | Relay application guides; IEEE C37.91 |
| Typical 87N sensitivity | 5–10% of rated winding current, or 10–20% of NGR current | Industry practice; depends on CTs and scheme |
| 87T coverage, 5 MVA 34.5–4.16 kV, 400 A NGR, 0.3 pu pickup | Detects only faults in the top ~5% of the wye winding | Keentel worked example 2 |
| 87N coverage, same transformer, high-impedance scheme | Detects faults down to ~6% from the neutral (~94% coverage) | Keentel worked example 5 |
| NERC maintenance standard for BES protection systems | PRC-005-6 | NERC Reliability Standards |
The core ideas in one table
| Idea | What it means in practice |
|---|---|
| 87T measures phase current imbalance across the transformer | It compares compensated currents on every winding; any internal fault large enough to exceed the restrained characteristic trips. |
| 87T must remove zero-sequence current on grounded-wye windings | Otherwise an external ground fault would cause a false trip; the cost is lost sensitivity to internal ground faults on that winding. |
| A resistance-grounded winding limits ground fault current | Fault current is roughly proportional to the distance of the fault from the neutral, and cannot exceed the NGR rating. |
| Reflected current falls with the square of position | A fault at fraction x of the winding produces about x² of the maximum current on the delta side, because both the voltage driving the fault and the turns ratio shrink. |
| 87N compares neutral current with the residual of the phase currents | It sees only ground faults inside the wye winding and its leads; it is stable for external faults and blind to phase faults and the delta winding. |
| 87N is set in amperes, not in per unit of transformer rating | Its sensitivity is independent of the transformer MVA, which is why it works where 87T cannot. |
| CT performance governs both elements | High-impedance 87N needs matched CTs with adequate knee-point voltage; 87T needs CTs that will not saturate badly on heavy through faults. |
| "Full coverage" still needs other protection | Turn-to-turn faults involving few turns, core faults and incipient faults need sudden pressure (63), gas accumulation, negative-sequence differential (87Q) or condition monitoring. |
Fact check: common simplifications
Explanations of 87T and restricted earth fault protection circulate widely in international material, often using IEC voltage classes (for example a 5 MVA transformer with a 6.6 kV secondary and a 400 A resistor, which gives 9.53 Ω — the arithmetic is correct). The principles are sound, but several statements need correction or expansion for US practice.
| Common statement | Keentel's engineering check |
|---|---|
| "Restricted earth fault is device 64." | In IEEE C37.2, device 64 is a ground detector relay, most often applied to generator stator and field ground detection. In US practice restricted ground fault on a transformer is a differential element and is designated 87N, 87G or 87GD. Using 64 on US drawings causes confusion in relay settings, test plans and NERC documentation. |
| "The transformer is Dyn11." | Dyn11 is the IEC vector group in which the low-voltage side leads the high-voltage side by 30°. The ANSI standard delta–wye connection in IEEE C57.12.00 has the low-voltage side lagging by 30°, which corresponds to IEC Dyn1. The difference matters when you select the phase-compensation setting in a numerical 87T relay. |
| "87T filters out zero-sequence current." | Correct for a grounded-wye winding — the relay (or delta-connected CTs on older schemes) must remove zero-sequence current so that external ground faults do not cause a trip. It is the main reason 87T loses sensitivity to wye-winding ground faults, and it applies equally to solidly grounded windings. |
| "REF is sensitive to 5–10% of rated current." | Achievable, but the sensitivity is set by the CTs, the scheme and the relay, not by the transformer rating. For a high-impedance scheme the primary operating current must be calculated from the relay current, CT magnetizing currents and any voltage limiter leakage. On a 400 A resistance-grounded system it is often better to express sensitivity as a percentage of NGR current. |
| "87T may miss faults near the neutral." | Understated. With a 400 A resistor on a winding rated 694 A, a 0.3 pu 87T misses faults in about 95% of the winding. On larger transformers with the same resistor, 87T may not see a wye-winding ground fault anywhere in the winding. |
| "REF can't see phase faults or the delta winding." | Correct. 87N is restricted to ground faults within the zone bounded by the phase and neutral CTs on one winding. Delta-winding faults to ground on an ungrounded or impedance-grounded high-voltage system are seen by 87T and by high-side ground detection. |
| "87T plus REF equals full coverage." | Close, but not complete. A short-circuit of a few turns can produce terminal currents too small for either element; sudden pressure relays, gas accumulation relays, negative-sequence differential and dissolved gas analysis remain essential. |
| "The NGR limits fault current to 400 A." | True only for faults at the winding terminals with negligible fault resistance. Faults nearer the neutral, or with arc and ground-path resistance, produce less. |
| "REF is not needed on solidly grounded windings." | Not quite. A solidly grounded winding has high fault current over most of its length, but 87T can still miss faults in the lowest few percent of the winding. Restricted ground fault adds sensitivity there at modest cost. |
Eight findings for decision makers
1. Low-resistance grounding is the reason 87N exists. The very feature that protects equipment and people on 4.16, 13.8 and 34.5 kV systems — limiting ground fault current to a few hundred amperes — hides internal ground faults from the transformer differential.
2. The coverage gap can be calculated, and should be. A single page of calculation shows whether 87T covers 5% or 50% of a wye winding. Keentel includes that calculation in every transformer protection settings package.
3. Bigger transformers are worse, not better. With the same 400 A resistor, a 33 MVA 69–13.8 kV transformer produces a maximum 87T differential current of only about 0.17 pu — below any practical minimum pickup.
4. High-impedance 87N is simple, fast and sensitive, but unforgiving of CT mistakes. Matched ratios, adequate knee-point voltage, correct polarity and a voltage limiter are not optional.
5. Low-impedance 87N in numerical relays is flexible, but must be set carefully. It tolerates different CT ratios and shares CTs with 87T, but needs proper directional supervision and an understanding of CT saturation during external faults.
6. Both elements fail most often because of wiring, not settings. Reversed neutral CT polarity is the classic restricted ground fault failure mode; it can sit undetected until the first external ground fault.
7. Backup ground protection on the NGR is still required. A neutral time-overcurrent relay (51G) protects the resistor and backs up feeder ground protection; NGR monitoring detects an open resistor that would leave the system ungrounded.
8. Evidence matters. For BES transformers, PRC-005-6 requires documented maintenance of relays, CTs, voltage and current sensing, dc supply and trip paths; a missing 87N test record is a compliance finding even if the relay works.
Key terms
| Term | Meaning |
|---|---|
| 87T | Transformer differential relay; compares currents entering and leaving the transformer after ratio and phase compensation. |
| 87N / 87G / 87GD | Restricted ground fault (ground differential) relay on one grounded-wye winding; compares neutral current with the residual of the phase currents. |
| REF | Restricted earth fault — the international name for the same function. |
| NGR | Neutral grounding resistor; limits ground fault current on low-resistance grounded systems. |
| Low-resistance grounding (LRG) | Grounding through a resistor sized for a few hundred to about 1,000 A, typically with a 10 s rating. |
| High-resistance grounding (HRG) | Grounding through a resistor sized for less than about 10 A; ground faults are alarmed rather than tripped. |
| Minimum pickup (O87P) | The smallest differential current, in per unit of tap, that the 87T can operate on. |
| Slope (restraint) | The ratio of operate to restraint current above which 87T trips; accommodates CT errors, tap changer range and magnetizing current. |
| Zero-sequence removal | Mathematical (or delta-CT) elimination of zero-sequence current from 87T on grounded windings. |
| High-impedance scheme | A differential scheme in which CT secondaries are paralleled across a high-impedance voltage-operated relay. |
| Low-impedance (biased) scheme | A numerical scheme that calculates differential and restraint quantities from individually measured CT currents. |
| Knee-point voltage | The CT secondary voltage above which magnetizing current rises sharply; defined differently in IEEE C57.13 and IEC practice. |
| Voltage limiter | A nonlinear resistor (often a metal-oxide varistor) across a high-impedance relay to limit peak secondary voltage during internal faults. |
| x | In this guide, the fault position measured from the neutral as a fraction of the wye winding (x = 0 at the neutral, x = 1 at the line terminal). |
Part B — Transformer Differential and Restricted Ground Fault: The Engineering Guide
1. Transformer faults and the layers of protection
A power transformer is a reliable piece of equipment, but when it fails internally the consequences are expensive: a damaged core and windings, oil fire risk, long replacement lead times and, for many US transformer classes today, delivery times measured in years rather than months. The purpose of transformer protection is not to save the faulted winding — once an arc has started inside the tank, the winding is usually lost — but to limit damage to the core, tank and surrounding equipment, to prevent tank rupture and fire, and to clear the fault before it disturbs the rest of the power system.
Internal faults fall into a small number of categories:
- Winding-to-ground faults, from a winding or lead to the core or tank. These are the most common internal electrical faults and are the main subject of this guide.
- Phase-to-phase faults between windings of different phases. Less common in three-phase core-type designs because of the physical separation, but severe when they occur.
- Turn-to-turn and layer faults within one winding, often starting from insulation degradation, moisture, overheating or a through-fault that mechanically displaces the winding.
- Bushing and lead faults inside the zone of the differential CTs but outside the tank.
- Core faults, such as failed core insulation or circulating currents, that create local heating without a large change in terminal currents.
- Tap changer faults, in either the de-energized tap changer or the load tap changer (LTC) compartment.
Turn-to-turn and core faults are particularly important because they can begin with very small terminal current changes. A short circuit of a few turns produces a very large current in the shorted turns — enough to vaporize copper and decompose oil — while the current at the transformer terminals changes by only a few percent of rating.
IEEE C37.91, the IEEE guide for protecting power transformers, describes a layered approach. Keentel uses the following as a baseline for transformers above a few MVA:
| Layer | Device (IEEE C37.2) | What it detects | Typical speed |
|---|---|---|---|
| Transformer differential | 87T | Phase faults, most heavy internal faults, bushing and lead faults | 1–2 cycles |
| Restricted ground fault | 87N / 87G | Ground faults in a grounded-wye winding, especially near the neutral | 1–2 cycles |
| Sudden pressure | 63 (sudden pressure relay) | Rapid pressure rise from internal arcing, including turn-to-turn faults | A few cycles |
| Gas accumulation / Buchholz | 63 / 80 / 71 (by design) | Slow gas generation from incipient faults; severe surges on conservator units | Seconds to hours |
| Phase overcurrent | 50/51 | Backup for internal and external phase faults; through-fault protection | Time delayed |
| Ground overcurrent | 50G/51G, 51N | Backup for ground faults; NGR thermal protection | Time delayed |
| Thermal | 26, 49 | Oil and winding temperature | Minutes |
| Overexcitation | 24 | Volts-per-hertz above rating | Seconds to minutes |
The 87T and 87N elements are the primary electrical protection for internal faults. The others either detect faults that the electrical elements cannot (63 and gas devices for turn-to-turn and incipient faults), back them up (50/51, 51G), or protect the transformer from abnormal operating conditions (26, 49, 24). Keentel's guide on sudden pressure and Buchholz relays, written for PRC-005-6 maintenance, covers the mechanical devices in detail; this guide concentrates on the two differential elements.
How Keentel Engineering helps here. Keentel starts every transformer protection project with a protection philosophy document: which faults each device must detect, which devices trip which breakers and lockout relays, which functions are primary and which are backup, and how each relates to PRC-005-6 maintenance intervals. That document becomes the basis for settings, test plans and compliance evidence.
2. How the transformer differential (87T) works
A differential relay compares the currents entering and leaving a protected zone. For a transmission line or bus the comparison is straightforward: what goes in must come out. A transformer complicates the comparison in three ways:
1. Different voltages and currents on each winding. The relay must scale each winding's current to a common base — the "tap" or "matching" factor.
2. Phase shift. A delta–wye transformer shifts phase currents by 30°. The relay must apply a compensation so that currents on both sides are compared in phase.
3. Zero-sequence current. A grounded-wye winding can carry zero-sequence current that has no counterpart in the delta winding's line currents. The relay must remove it from the comparison on the grounded side, or an external ground fault will look like an internal fault.
In addition, a transformer draws magnetizing current that appears on one side only. In steady state this is small (well under 1% of rating on modern cores), but at energization the inrush current can reach many times rating. Overexcitation also increases magnetizing current. The relay must be secure during both.
Numerical 87T relays compute, for each phase, an operate (differential) current and a restraint current from the compensated winding currents I₁ and I₂ (in per unit of tap):
Different manufacturers use different restraint definitions — the scalar sum, the average, or the maximum of the winding currents — so the factor k and the numerical meaning of the slope setting differ between relays. The trip condition is that the operate current exceeds the minimum pickup and lies above a slope (or dual-slope) characteristic:
A dual-slope characteristic uses a low first slope (typically 25–35%) for light through-currents and a steeper second slope (typically 50–80%) above a breakpoint, to keep the relay stable when CTs begin to saturate on heavy external faults.
In a numerical relay the tap for each winding is calculated from the transformer's maximum rating, the winding's line-to-line voltage and the CT ratio:
Many relays calculate taps automatically. The engineer still needs to check that the ratio of the largest to smallest tap is within the relay's permitted range and that each tap lies within the relay's allowed current range.
The transformer used throughout this guide is a 5 MVA, 34.5–4.16 kV delta–wye unit, low-voltage winding grounded through a 400 A, 10 s resistor. CTs are 200:5 on the 34.5 kV side (CTR 40) and 1000:5 on the 4.16 kV side (CTR 200).
| Quantity | 34.5 kV winding | 4.16 kV winding |
|---|---|---|
| Rated line current | 83.7 A | 693.9 A |
| CT ratio | 200:5 (CTR 40) | 1000:5 (CTR 200) |
| Tap = 5,000 / (√3 × kV × CTR) | 2.092 A | 3.470 A |
| Secondary current at rating | 2.09 A | 3.47 A |
The tap ratio is 3.470 / 2.092 = 1.66, well within the typical relay limits. Both CTs operate well below their 5 A rating at full load, which leaves room for emergency loading and keeps CT burden voltages low during faults.
The slope must exceed the worst-case false differential current during load and through faults, expressed as a percentage of restraint. Keentel builds the error budget explicitly:
| Error source | Allowance |
|---|---|
| Load tap changer range (±10%) | 10% |
| CT error, high side (C-class accuracy within rating) | 5% |
| CT error, low side | 5% |
| Relay measurement error | 2% |
| Tap mismatch after rounding | 1% |
| Total | 23% |
A first slope of 30% gives a margin of 7 percentage points over the worst-case steady-state error. A second slope of 60–70% above about 3–6 times tap covers the additional error when one CT approaches saturation. On a transformer without an LTC, a first slope of 25% is often adequate.
Inrush current is rich in second harmonic, overexcitation current in fifth harmonic. Traditional relays block or restrain the differential element when the second harmonic exceeds a percentage of the fundamental — 15% to 20% is a common setting — and block on fifth harmonic above about 35%.
During a field energization of a transformer with a low-loss, high-permeability core, the recorded inrush on one phase showed a fundamental of 4.2 pu of tap and a second harmonic of 0.42 pu — a ratio of 10%. A relay with independent per-phase blocking at 15% would not have blocked on that phase. Modern cores frequently produce second-harmonic ratios below 15% on one or more phases. Practical solutions include cross-phase blocking or averaging (blocking all phases if any phase has sufficient harmonic), lower harmonic thresholds with waveshape-based supervision, and dc-offset or "gap detection" methods available in many numerical relays. Keentel's guide to transformer inrush versus internal faults treats this subject in detail.
The important point for this guide is the effect on restricted ground fault protection: magnetizing inrush on a delta–wye transformer energized from the delta side produces little or no current in the wye-winding neutral, so a correctly applied 87N element is inherently stable during inrush. That is one reason 87N can be set far more sensitively than 87T.
Keentel Service Spotlight — Transformer differential settings study. Keentel calculates taps, phase compensation, minimum pickup, dual-slope characteristic, harmonic blocking or restraint, unrestrained (87U) pickup and CT requirements from the nameplate, CT data and short-circuit study. Every setting is justified in writing and checked against relay-specific limits, so the settings sheet can be defended to the asset owner, the Regional Entity and the next engineer who touches it.
How Keentel Engineering helps here. Keentel's settings packages for 87T include a through-fault stability check for every external fault location, an inrush review against manufacturer and field data, and a sensitivity check that tells you — in percent of each winding — what the element can and cannot see.
3. Phase shift, ANSI connections and zero-sequence removal
IEEE C57.12.00 specifies the standard angular displacement for three-phase transformers in the United States: for delta–wye and wye–delta connections the low-voltage side lags the high-voltage side by 30°. In IEC notation, where the clock number gives the low-voltage phasor position in 30° steps lagging the high-voltage phasor, that connection is Dyn1(one o'clock). The IEC group Dyn11 has the low-voltage side leading by 30°. Dyn11 is the common distribution connection in many IEC markets; Dyn1 is the ANSI standard.
This is not merely notation. A numerical 87T relay applies a compensation matrix — selected by a setting that may be called the winding compensation, phase-shift compensation or connection setting — to rotate one or more winding currents into phase. Choosing the matrix for Dyn11 on an ANSI Dyn1 transformer produces a 60° error between the two windings and a large standing differential current at load. The error is usually caught at the first load check after energization — if a load check is performed. When the compensation is applied but the CTs are wired with the wrong phase sequence or polarity, the result can be equally serious and harder to diagnose. Keentel's commissioning procedures therefore include a calculated phasor diagram for every 87T installation that shows the expected secondary currents, angles and differential at a known load before the first load reading is taken.
Some US transformers are built with non-standard displacements, and some legacy installations use the old practice of connecting the CTs on the wye side in delta (and on the delta side in wye) to perform the phase shift and zero-sequence removal externally. When a numerical relay replaces an electromechanical scheme, the engineer must decide whether to keep the delta-connected CTs (and set the relay's internal compensation accordingly) or rewire them in wye and compensate internally. Both are valid; mixing the two is a frequent source of misoperations.
Consider an external single-line-to-ground fault on the 4.16 kV feeder side of our delta–wye transformer. Ground fault current flows from the fault, through the ground return path, into the NGR, up through the neutral and into the wye winding, and back out to the fault through the faulted phase. The 4.16 kV phase CTs see the fault current in one phase. The 34.5 kV delta line currents see the reflected current in two phases, but the zero-sequence component circulates inside the delta and does not appear in the 34.5 kV line currents at all.
If the relay compared raw phase currents, the low-voltage side would contain a zero-sequence component with no counterpart on the high side and the relay would see a large differential current for a fault outside its zone. Therefore the 87T must remove zero-sequence current from the grounded-wye winding's currents. In a numerical relay this is done by the compensation matrix — the same matrix that provides the phase shift for a delta–wye transformer inherently subtracts the zero-sequence component. In electromechanical practice it was done by connecting the wye-side CTs in delta.
Removing zero-sequence current from the wye side makes 87T stable for external ground faults. It also means that, for an internal ground fault in the wye winding, the relay responds only to the positive- and negative-sequence components of the fault current reflected into the delta side. For a single-line-to-ground fault the zero-sequence component is one third of the fault current, so the relay loses part of its sensitivity before any other effect is considered. The rest of the loss comes from the way current is reflected through the winding, discussed in Section 5.
Now consider a fault from a 34.5 kV bushing lead to ground, inside the 87T zone. The 34.5 kV system is solidly grounded at the source substation and the available single-line-to-ground fault current at this location is 8 kA. Fault current flows from the source into the faulted lead and to ground; very little flows through the transformer.
- The 34.5 kV CTs carry about 8,000 / 40 = 200 A secondary in the faulted phase. Referred to the tap, this is about 8,000 / 83.7 ≈ 96 pu.
- The 4.16 kV CTs see essentially nothing.
- The 87T operates immediately; in fact the unrestrained (87U) element operates.
- The 87N element on the 4.16 kV winding sees nothing. Restricted ground fault protection on the low-voltage winding is blind to the delta winding and to the high-voltage leads.
This example illustrates the complementary nature of the two elements: 87T is excellent for faults that draw large current from the system; 87N is excellent for faults whose current is limited by the grounding resistor.
How Keentel Engineering helps here. Keentel verifies phase compensation from the transformer nameplate vector diagram — not from assumptions — and prepares a commissioning phasor sheet showing expected relay currents for a load check and for a primary-injected test, so that polarity and compensation errors are caught before the transformer carries load.
4. How the wye winding is grounded
The grounding of a wye winding determines both the ground fault current and the protection needed. IEEE 142 (the Green Book) and IEEE C62.92 describe the options:
| Grounding method | Typical ground fault current | Typical use in US practice | Ground fault protection |
|---|---|---|---|
| Solid | Comparable to or larger than three-phase fault current | Utility distribution (13.8, 34.5 kV multigrounded), transmission | 50/51N, 87T, optional 87N |
| Low-resistance (LRG) | 200–1,000 A, often 400 A for 10 s | Industrial 4.16–13.8 kV, data center MV, solar/BESS 34.5 kV collector systems (some designs) | 87N, 51G on NGR, feeder 50/51N |
| High-resistance (HRG) | Under about 10 A | Industrial 480 V and some 4.16 kV systems that must keep running | Alarm (59N, 51N), selective location; 87N usually not practical |
| Reactance | 25–100% of three-phase fault current | Generators, some utility systems | 51N, 87N |
| Ungrounded | Capacitive charging current only | Legacy industrial | Ground detection only |
Note that on many US solar and BESS plants the 34.5 kV collector system is solidly grounded through the wye winding of the main power transformer, or effectively grounded through grounding transformers; low-resistance grounding is also used. The protection approach depends on which choice was made, which is why Keentel's collector-system designs document the grounding philosophy explicitly.
For a 4.16 kV system grounded for 400 A:
| Quantity | 4.16 kV, 400 A | 13.8 kV, 400 A |
|---|---|---|
| Line-to-neutral voltage | 2,401.8 V | 7,967.4 V |
| Resistance | 6.00 Ω | 19.92 Ω |
| Power at rated current | 961 kW | 3,187 kW |
| Energy for 10 s | 9.6 MJ | 31.9 MJ |
The 10 s rating defined in IEEE C57.32 means that the resistor element must absorb that energy without exceeding its permitted temperature rise. Two practical consequences follow:
- The ground protection must clear within the resistor's rating, with margin, for every fault the resistor might carry. This governs the 51G time dial on the NGR (Section 11).
- The resistor is a component of the protection system. If it fails open, the system becomes ungrounded; a second ground fault on another phase becomes a phase-to-phase fault through ground. NGR monitoring is therefore an important part of the scheme.
Because the resistor is large compared with the transformer's zero-sequence leakage impedance and the system's positive- and negative-sequence impedances, the ground fault current at the winding terminals is essentially:
where R_f is the fault resistance. For a bolted fault at the terminals the current is just under 400 A. For an arcing fault with a few ohms of arc and ground-path resistance — common in cable terminations and motor connection boxes — the current can be considerably smaller. A fault inside the winding is smaller still, as the next section shows.
Keentel Service Spotlight — Grounding design and NGR sizing. Keentel selects grounding methods and NGR ratings from system charging current, protection sensitivity, equipment insulation, arc-flash and personnel safety requirements; specifies NGR enclosures, current transformers and monitoring; and coordinates NGR thermal ratings with the ground protection. For solar, BESS and data center projects, we document the grounding philosophy so that every downstream protection decision follows from it.
How Keentel Engineering helps here. Keentel's short-circuit studies include ground fault currents at every bus and, where resistance grounding is used, the fault-current profile within transformer windings — the input needed to decide whether 87N is required and how sensitive it must be.
5. The physics of a ground fault inside a wye winding
Consider a ground fault at a point inside the wye winding, a fraction x of the winding's turns measured from the neutral (x = 0 at the neutral, x = 1 at the line terminal). The voltage driving current into the fault is the voltage induced in the x portion of the winding — approximately x times the line-to-neutral voltage. On a resistance-grounded winding the resistor dominates the circuit impedance, so:
A fault halfway down the winding drives about 200 A in our 400 A example; a fault 10% from the neutral drives about 40 A.
The fault current flows only in the x portion of the faulted winding, so its ampere-turns are x × N_LV × I_f. The delta winding on the same core leg must supply equal and opposite ampere-turns:
Because the voltage driving the fault and the effective turns ratio both shrink with x, the current reflected into the delta winding is proportional to x². In a delta–wye transformer a single loaded low-voltage phase corresponds to a single delta winding, whose current appears in two of the high-voltage line conductors, so two 87T phase elements see it.
For our 5 MVA, 34.5–4.16 kV, 400 A transformer, with the high-voltage rated line current of 83.67 A as the tap base:
| Quantity | Value |
|---|---|
| N_LV / N_HV per phase = 2,401.8 / 34,500 | 0.06962 |
| HV line current for a fault at x | 400 × 0.06962 × x² = 27.85 x² A |
| Differential current in per unit of tap | 27.85 x² / 83.67 = 0.333 x² pu |
| Maximum (fault at the line terminal, x = 1) | 0.333 pu |
The low-voltage CTs see no fault current (the fault current returns through the neutral, not the line CTs), so the full reflected current is differential current. Solving 0.333 x² = pickup:
| 87T minimum pickup | Lowest detectable fault position | Portion of wye winding not covered |
|---|---|---|
| 0.30 pu | x = 0.949 | 94.9% |
| 0.20 pu | x = 0.775 | 77.5% |
| 0.15 pu | x = 0.671 | 67.1% |
The result is stark. Even with an aggressive 0.15 pu minimum pickup, the 87T cannot see a ground fault in two thirds of the wye winding. With the common 0.3 pu setting it is effectively blind to wye-winding ground faults, and only a bolted fault at the very terminal produces enough differential current. The same transformer with a 1,000 A resistor would produce 0.83 x² pu, improving coverage at 0.3 pu to about 40% — still far from complete.
Two further effects make the real situation worse than the calculation. First, any fault resistance reduces I_f below x × I_NGR. Second, load current adds restraint, raising the operate threshold on the slope characteristic for a transformer that is loaded at the time of the fault.
Utilities and industrial plants often use the same 400 A grounding standard across many transformer sizes. For a 20/26.7/33.3 MVA (ONAN/ONAF/ONAF), 69–13.8 kV delta–wye transformer with a 400 A, 19.92 Ω resistor:
| Tap base | LV rated current | Maximum 87T differential (fault at terminal) |
|---|---|---|
| 20 MVA (self-cooled) | 836.7 A | 0.276 pu |
| 33.3 MVA (top forced-cooled) | 1,393 A | 0.166 pu |
Because numerical relays are normally set on the maximum nameplate rating, the maximum differential current for a 13.8 kV winding ground fault anywhere in the winding is only about 0.17 pu. With a 0.3 pu minimum pickup, 87T cannot detect a 13.8 kV winding ground fault anywhere in the winding. For this transformer, 87N is not an enhancement; it is the only fast electrical protection for wye-winding ground faults. For comparison, the commonly circulated international example described in Part A (5 MVA, 400 A resistor, IEC-class secondary voltage) gives 0.528 x² pu, so a 0.3 pu 87T misses about 75% of the winding; the US examples above are more severe because the resistor current is a smaller fraction of the winding's rated current.
On a solidly grounded wye winding there is no resistor to dominate the circuit. The fault current is limited by the leakage reactance between the shorted portion of the winding and the rest of the transformer, and by the system impedance reflected through the effective turns ratio. As the fault moves toward the neutral, the driving voltage falls, but the leakage reactance of the shorted portion falls even faster. The classic result, shown in published curves in the protection literature, is that the winding fault current is high at the terminal, passes through a minimum somewhere in the lower half of the winding, and rises again close to the neutral.
Using the illustrative curve in Figure 2, the high-voltage line current seen by the 87T is above a 0.3 pu pickup for faults down to about 9% of the winding from the neutral. The 87T therefore covers roughly 90% of a solidly grounded wye winding — much better than the resistance-grounded case, but not 100%. Restricted ground fault protection on a solidly grounded winding detects faults in that lowest portion and responds faster and more securely to low-level faults near the neutral. Whether it is justified depends on the transformer's size and importance; Keentel typically recommends it on GSUs, main power transformers at IBR plants and critical substation transformers, where the cost is a neutral CT and a few relay settings.
Keentel Service Spotlight — Winding coverage analysis. For every transformer we protect, Keentel calculates the percentage of each grounded winding covered by 87T and by 87N, for bolted faults and with a stated fault resistance, and documents the result in the settings report. Owners see, in one table, which parts of the transformer are protected by which element.
How Keentel Engineering helps here. Keentel uses the coverage analysis to make a reasoned recommendation: add 87N, lower the 87T minimum pickup within safe limits, change the CT ratio, or accept a documented residual risk. The recommendation and its basis go into the protection philosophy so that future reviewers understand the decision.
6. Restricted ground fault (87N): the principle
Restricted ground fault protection is a differential scheme on one grounded-wye winding, restricted to ground faults. It compares:
- the current in the neutral connection, measured by a CT between the winding neutral and the NGR (or ground); and
- the residual current of the three line CTs on the same winding, that is, the sum of the three phase currents, equal to 3I₀.
For a ground fault outside the zone — on the 4.16 kV feeders, for example — the same zero-sequence current flows through the neutral CT and through the phase CTs. With correct polarities the two measurements cancel and the differential is zero. For a ground fault inside the zone — in the wye winding or its leads between the phase CTs and the neutral — current flows through the neutral CT but not through the phase CTs (or flows through them in the opposite direction if another ground source exists on the low-voltage system). The differential equals the fault current and the element operates.
The 87N element responds only to zero-sequence (ground) current that enters the zone through the neutral. It therefore:
- does not see phase-to-phase or three-phase faults, which involve no neutral current;
- does not see faults on the delta winding, which cannot drive current through the wye neutral;
- does not see turn-to-turn faults that do not involve ground;
- is inherently stable for magnetizing inrush and overexcitation, because magnetizing current in a delta–wye transformer energized from the delta side does not flow in the wye neutral; and
- is unaffected by load current and by the transformer's tap position.
Those properties are exactly what allows 87N to be set in tens of amperes primary, independent of the transformer's MVA rating, while 87T must be set in tenths of a per unit of a rating that may be thousands of amperes.
Restricted ground fault elements are built in two ways:
| Feature | High-impedance 87N | Low-impedance (biased) 87N |
|---|---|---|
| Measurement | Paralleled CT secondaries across a voltage-operated relay | Individual CT currents measured by a numerical relay |
| CT ratios | Must be identical on all four CTs | May differ; relay scales them |
| CT class | Matched, low-leakage, with known knee-point voltage and winding resistance | Normal protection-class CTs; can share with 87T |
| Stability for external faults | By design: a saturated CT presents a low impedance, diverting current from the high-impedance relay | By restraint and directional supervision |
| Sensitivity | Very good; set by relay current and CT magnetizing currents | Good; set by relay minimum pickup and CT ratio |
| Speed | Typically 1–2 cycles | Typically 1–2 cycles |
| Typical use in US practice | Autotransformers, large GSUs, critical substations, retrofits with dedicated CTs | Multifunction transformer relays on new installations |
7. High-impedance restricted ground fault
In a high-impedance scheme the secondaries of the three phase CTs and the neutral CT are connected in parallel, with polarities arranged so that through current circulates between the CTs and does not enter the relay branch. A voltage-operated relay with a high internal impedance (typically a few hundred to a few thousand ohms) is connected across the paralleled leads.
For an external fault with perfect CTs, the currents circulate and the voltage across the relay is essentially zero. The design case is the external fault in which one CT saturates completely. A fully saturated CT has negligible magnetizing impedance and behaves like its winding resistance. The healthy CT then drives its secondary current through the lead resistance and the saturated CT's winding resistance, producing a voltage across the relay branch. The relay is set above the maximum possible value of that voltage:
where I_F,sec is the maximum external fault current referred to the CT secondary, R_CT is the CT secondary winding resistance and 2R_L is the loop lead resistance from the CT to the relay junction point.
Data for our 5 MVA transformer, 4.16 kV winding:
| Item | Value |
|---|---|
| Transformer impedance | 6.5% on 5 MVA |
| Maximum external through-fault (three-phase, infinite source) | 693.9 / 0.065 = 10,676 A |
| Phase and neutral CTs | 1000:5, identical, multi-ratio C400, used on full ratio |
| CT secondary resistance | 0.50 Ω |
| One-way lead resistance (about 150 ft of #10 AWG) | 0.15 Ω |
| Relay impedance at setting | 2,000 Ω |
Stability voltage:
- I_F,sec = 10,676 / 200 = 53.4 A
- V_s ≥ 53.4 × (0.50 + 0.30) = 42.7 V
- Setting chosen: 60 V, a 40% margin over the theoretical minimum.
Knee-point requirement: the CTs must be able to develop at least twice the setting voltage before saturating, so V_k ≥ 120 V. A 1000:5 C400 CT on full ratio typically has an IEEE knee-point voltage well above that; the actual excitation curve from the CT manufacturer or a field excitation test must confirm it.
Primary operating current — the sensitivity — is the CT ratio times the sum of the relay current, the magnetizing currents of all four CTs at the setting voltage and any voltage-limiter leakage:
With I_r = 60 / 2,000 = 0.030 A, I_e = 0.020 A per CT at 60 V (from the excitation curve), n = 4 and I_lim = 0.005 A:
- I_op,primary = 200 × (0.030 + 0.080 + 0.005) = 23 A
- That is 5.75% of the 400 A NGR current and 3.3% of the winding's rated current.
- Because I_f(x) ≈ x × 400 A, the element detects faults down to x = 23 / 400 = 0.058 — it covers about 94% of the winding.
Note how the CT magnetizing current dominates the sensitivity. If the CTs had been chosen with poor excitation characteristics, or if additional CTs were paralleled into the scheme, the primary operating current would rise. If more sensitivity is needed, a deliberately added shunt resistor is sometimes used to raise — not lower — the operating current to a defined value; the opposite problem (too sensitive) is rare.
For an internal fault the CT secondary current is forced into the high-impedance relay. If the CTs did not saturate, the relay voltage would be the fault current times the relay impedance — in our example (400 / 200) × 2,000 = 4,000 V. The CTs will in fact saturate, producing narrow voltage peaks. A commonly used estimate of the peak secondary voltage is:
With V_k = 280 V and V_f = 4,000 V, V_peak ≈ 2,900 V. Many application guides recommend a voltage limiter — a metal-oxide nonlinear resistor — when the estimated peak approaches about 3 kV, to protect CT secondary insulation, wiring and the relay. Keentel's practice is to include the limiter whenever the calculated peak exceeds about 2 kV and to include its leakage current in the sensitivity calculation, as above. The limiter's energy rating must also be checked for the internal-fault duration.
- Identical CT ratios on all four CTs. Multi-ratio CTs must all be connected on the same tap, documented and locked.
- Known CT parameters: secondary winding resistance and excitation curve for every CT, measured at commissioning.
- Dedicated CT cores whenever possible; sharing high-impedance CTs with metering or other relays introduces burden and possible open-circuit risk.
- A single junction point, with lead resistances measured, close to the CTs.
- CT supervision: an open CT secondary in a high-impedance scheme produces a differential current at load; some relays include a supervision element that alarms on a small standing voltage.
- Shorting provision: test switches that allow the relay to be isolated without open-circuiting the CTs.
Keentel Service Spotlight — High-impedance 87N design. Keentel specifies the CTs (ratio, accuracy class, knee point, winding resistance), the junction point and wiring, the relay setting voltage, the voltage limiter and the expected primary operating current, and includes a field excitation test and a primary injection test in the commissioning plan to prove that the as-built sensitivity matches the design.
How Keentel Engineering helps here. When an existing scheme misoperates, Keentel recalculates the stability voltage with measured lead and CT resistances and compares it with the setting; we frequently find that a later change — a CT ratio change, an added lead run or an extra device on the CT circuit — eroded the original margin.
8. Low-impedance (biased) restricted ground fault
Most modern multifunction transformer relays include a low-impedance restricted ground fault element. The relay measures each phase CT and the neutral CT individually, computes the residual current from the phase CTs, scales the neutral current to the phase CT ratio, and forms a differential and a restraint quantity. Many implementations add a directional comparison between the residual current (3I₀ from the phase CTs) and the neutral current:
- For an external ground fault, the residual and neutral currents are equal and, with the relay's polarity convention, opposite in direction — the element restrains.
- For an internal ground fault with no other ground source on the low-voltage system, the residual current from the phase CTs is near zero, and the element trips on the neutral current alone above its pickup.
- For an internal fault on a low-voltage system with other ground sources (for example a second grounded transformer or a grounding bank on the same bus), the residual current flows into the zone and is in phase with the neutral current — the element trips.
Directional supervision makes the element secure against false residual currents caused by phase-CT saturation during heavy external phase faults, which is the main threat to low-impedance 87N.
On many installations the neutral CT is sized for the NGR rating while the phase CTs are sized for load. Take phase CTs of 1000:5 and a neutral CT of 400:5 (CTR 80).
| External 4.16 kV ground fault, 400 A primary | Phase-a CT | Neutral CT |
|---|---|---|
| Secondary current | 400 / 200 = 2.0 A | 400 / 80 = 5.0 A |
| Neutral current scaled to phase CT ratio | — | 5.0 × 80 / 200 = 2.0 A |
| Differential (with correct polarity) | 0 A | — |
The relay setting must state both CT ratios correctly and the neutral CT polarity relative to the relay's convention. If the neutral CT ratio were entered as 1000:5 instead of 400:5, the relay would treat the 5.0 A neutral secondary current as 5.0 A on the phase base and see 3.0 A secondary (600 A primary) of false differential on every external ground fault — far above any pickup.
Keentel's typical starting points for a low-impedance 87N element, adjusted for each relay's algorithm, are:
- Pickup: 10–20% of NGR current on resistance-grounded windings, or 5–10% of winding rated current on solidly grounded windings, but not below the level supported by CT accuracy at low current.
- Slope or restraint: as recommended by the relay manufacturer for the expected maximum through-fault current and CT performance.
- Directional supervision: enabled, with the residual-current threshold set above the maximum false residual during external phase faults.
- Time delay: instantaneous or a few cycles; a short delay is sometimes used to ride through CT transients on external faults where CT performance is marginal.
Keentel Service Spotlight — Multifunction relay settings review. Keentel reviews 87T, 87N, 50/51, 51G and thermal settings in multifunction transformer relays as one coordinated set, checks every CT ratio and polarity entry against the as-built drawings, and runs the relay manufacturer's characteristic with the study fault currents to confirm security and sensitivity.
How Keentel Engineering helps here. Because low-impedance 87N shares CTs with 87T, a single wrong CT setting can disable or destabilize both. Keentel's settings packages include a CT data table — ratio, tap, class, polarity mark, wiring designation — that is verified in the field and kept with the settings record.
9. Current transformers for 87T and 87N
US relaying CTs are rated under IEEE C57.13 with a relaying accuracy class such as C400 or C800: the CT will deliver 20 times rated secondary current (100 A for a 5 A CT) into a standard burden with no more than 10% ratio error, and the class number is the secondary terminal voltage at that condition. The "C" designation indicates that the ratio error can be calculated from the excitation characteristic; "T" indicates it was determined by test. The IEEE knee point is defined on the excitation curve as the point where a 45° tangent touches the curve (for curves plotted on equal log-log scales).
International high-impedance schemes usually specify CTs as class PX (or the older class X), defined by the knee-point voltage, the magnetizing current at that voltage and the secondary winding resistance. The IEC knee point is defined differently — the point where a 10% increase in voltage produces a 50% increase in magnetizing current — and is higher on the same curve than the IEEE knee point. When an international design or vendor document specifies "Vk ≥ 2Vs", the engineer must state which definition applies and obtain the actual excitation curve. For US projects Keentel specifies C-class CTs with a required minimum excitation voltage at a stated magnetizing current, plus maximum secondary resistance — a specification that captures the PX intent in IEEE terms.
Steady-state CT performance is rarely the problem. The dc offset in an asymmetrical fault current can drive a CT into saturation within a cycle even when the symmetrical current is well inside its rating. IEEE C37.110 gives the classic requirement for avoiding saturation completely:
For the 1000:5 C400 phase CTs on the 4.16 kV side:
| Quantity | Value |
|---|---|
| Maximum through-fault secondary current | 53.4 A |
| Burden: CT winding 0.50 Ω + leads 0.30 Ω + relay 0.02 Ω | 0.82 Ω |
| Symmetrical secondary voltage | 53.4 × 0.82 = 43.8 V |
| X/R at the 4.16 kV bus | 15 |
| Voltage needed to avoid saturation with full offset | 43.8 × 16 = 700 V |
| 20-times check (100 A × 0.82 Ω) | 82 V, well under 400 V |
The CTs pass the steady-state check easily but would saturate during a fully offset maximum fault. For 87T, that is acceptable if the relay's dual-slope characteristic and any CT-saturation security logic keep it stable, which must be confirmed. For a high-impedance 87N it is expected and allowed — the scheme is designed for complete saturation of one CT. For a low-impedance 87N it is the main reason for directional supervision. Where a higher margin is wanted, the options are a higher ratio (if sensitivity allows), a higher accuracy class (C800), or lower burden (shorter leads, larger conductors).
On many substation designs the low-voltage phase CTs serve the 87T, the 87N, the feeder or main breaker overcurrent elements, and sometimes metering. Keentel's rule is that high-impedance 87N must have dedicated CT cores; low-impedance 87N may share cores with 87T in the same relay; and no relay CT circuit should share a core with revenue metering.
Keentel Service Spotlight — CT sizing and saturation study. Keentel calculates CT secondary voltages, saturation factors and time-to-saturate for every protective function on a transformer — 87T, 87N, 50/51 and breaker failure — using the actual fault currents, X/R ratios, lead lengths and relay burdens. The study produces a CT specification for new equipment and a risk assessment for existing CTs.
How Keentel Engineering helps here. For retrofit projects, Keentel reviews CT nameplates and field excitation test results to decide whether existing CTs can support a new numerical relay with 87N, or whether CT replacement or rewiring is required — before the relay panel is ordered.
10. Applications beyond the two-winding delta–wye transformer
Transmission transformers with a grounded-wye high-voltage winding (for example a 138–13.8 kV wye–wye transformer with a delta tertiary, or a 230–69 kV autotransformer) can also have restricted ground fault on the high-voltage side, using the high-voltage phase CTs and a neutral CT. Faults near the neutral end of a solidly grounded high-voltage winding share the same coverage limits discussed in Section 5.5.
An autotransformer's series and common windings share a single neutral. A high-impedance restricted ground fault scheme that sums the high-voltage, low-voltage and neutral CTs — sometimes called a "bus-type" or "winding" differential on the autotransformer — detects ground faults anywhere in the electrically connected windings and is a common US application for large 345–138 kV and 230–115 kV autotransformers. It requires identical CT ratios on all three sets of CTs, which must be specified with the autotransformer order. The delta tertiary, if present, is not covered by this scheme.
On systems where the main transformer winding is delta (for example a 34.5 kV collector system fed from a wye–delta main power transformer, or a 13.8 kV system fed from a delta winding), a zig-zag or wye–delta grounding transformer creates the neutral. Its protection usually includes overcurrent on the neutral, phase overcurrent on the grounding transformer supply, and often a restricted ground fault or zero-sequence differential element that compares neutral current with the residual of the grounding transformer's phase CTs.
A zig-zag grounding transformer for 400 A on a 4.16 kV system has a short-time rating equal to the line-to-neutral voltage times the neutral current:
Its continuous rating is much lower, set by the zero-sequence current that flows continuously because of system unbalance. Restricted ground fault on the grounding transformer covers faults in its windings, and its phase overcurrent elements must be set above the normal excitation and unbalance currents but below the internal fault current. A failed or tripped grounding transformer leaves the system ungrounded, so it is normally interlocked with, or trips, the source.
On utility-scale solar, wind and BESS plants, the main power transformer is commonly a 34.5 kV wye-grounded (or delta) collector winding and a 115, 138, 230 or 345 kV wye-grounded high-voltage winding, sometimes with a delta tertiary. A ground fault near the neutral end of either grounded winding has limited current, and inverter-based resources contribute little ground fault current of their own. Keentel's standard recommendation is to apply 87N on each grounded winding of the main power transformer in addition to 87T, with settings verified against the plant's actual grounding — including any grounding transformers on the collector bus.
Data center campuses commonly take service at 69–230 kV and step down to 13.8 or 34.5 kV, then to 4.16 kV or 480 V. Medium-voltage distribution is frequently low-resistance grounded at 13.8 kV, and the 13.8 kV wye winding of each substation transformer sees exactly the coverage problem in worked example 7. For the reliability expected of a Tier III or Tier IV facility, Keentel applies 87N on every low-resistance grounded transformer winding and verifies the NGR monitoring and backup ground protection as part of the electrical design review.
Keentel Service Spotlight — Data center and IBR substation protection design. Keentel designs and reviews protection for data center MV substations and IBR main power transformers, including grounding transformer protection, 87N on every grounded winding, NGR monitoring and coordination with inverter and UPS behavior during ground faults.
How Keentel Engineering helps here. Keentel's design reviews catch the most common gap on new MV substations: an NGR and neutral CT supplied with the transformer, a multifunction relay that includes 87N, and no one who ever enabled or set the 87N element.
11. Backup ground protection and NGR supervision
A time-overcurrent relay on the NGR neutral CT (51G, sometimes designated 51N) provides backup for low-voltage feeder ground faults and for internal wye-winding faults, and protects the resistor itself. It must:
- pick up below the minimum ground fault current it must detect (often 10–20% of NGR rating);
- coordinate with the largest downstream feeder ground element with an adequate coordination time interval;
- clear every fault within the NGR's thermal rating with margin; and
- trip the transformer (usually through the lockout relay) and, where appropriate, the low-voltage main breaker.
For the 400 A, 10 s NGR, with a 400:5 neutral CT and an IEEE very inverse curve (C37.112, U3):
| Element | Pickup (primary) | Multiple at 400 A | Time dial | Operate time at 400 A |
|---|---|---|---|---|
| Feeder 51N | 40 A | 10 | 1 | 0.69 s |
| NGR 51G | 80 A | 5 | 1 | 1.31 s |
The coordination interval is 0.62 s, comfortably above a typical 0.3 s minimum for numerical relays. The 1.31 s operate time is well within the 10 s NGR rating. At low fault currents the check is on energy rather than time: the NGR's I²t capability at rated current is 400² × 10 = 1.6 × 10⁶ A²s, so a 100 A fault can be carried for about 160 s, while the 51G with this setting clears it in about 35 s.
An NGR can fail open through element breakage, corrosion or a loose connection. Because a resistance-grounded system with an open resistor behaves as an ungrounded system, the failure is invisible in normal operation. NGR monitors continuously measure the resistor's continuity or the neutral-to-ground voltage (59N) and alarm or trip when the resistor is open or when a sustained neutral voltage indicates a fault that the overcurrent elements have not cleared. Keentel includes NGR monitoring on data center and industrial projects and recommends it as a retrofit wherever an NGR serves critical load.
How Keentel Engineering helps here. Keentel's coordination studies include the NGR as a protected element with its own damage curve, so that the 51G, feeder ground elements and 87N are coordinated as one system — and so that the resistor's 10 s rating is respected for every fault.
12. What neither element sees well: turn-to-turn and incipient faults
A short circuit of a few turns in a winding with hundreds or thousands of turns behaves like a transformer with a very high ratio loaded by a short circuit. The current in the shorted turns can be many times rated current, but the change in terminal current is roughly the shorted-turn current divided by the winding's turn count. For a fault involving 1% of the turns, the terminal current change can be only a few percent of rating — below any practical 87T minimum pickup and, unless the turns involve ground, invisible to 87N.
Many numerical transformer relays include a negative-sequence differential element. Because a turn-to-turn fault unbalances the transformer, the negative-sequence components of the compensated winding currents no longer balance, and the negative-sequence differential can be set much more sensitively than the phase differential (it is largely immune to balanced load and to tap-changer position). It must still be secured against CT saturation during external faults and against inrush. Keentel considers 87Q an effective, low-cost supplement for turn-to-turn faults on transformers above about 10 MVA.
Sudden pressure relays respond to the rapid pressure rise produced by arcing in oil and are the classic primary protection for turn-to-turn faults. Gas accumulation relays on conservator-type transformers detect slow gas generation from incipient faults. Dissolved gas analysis, online monitors and thermal monitoring detect developing problems long before they become faults. Keentel's companion guide on sudden pressure and Buchholz relays explains their application and PRC-005-6 maintenance requirements.
How Keentel Engineering helps here. Keentel's transformer protection reviews evaluate the whole fault spectrum — phase, ground, turn-to-turn, core and incipient — and recommend the combination of 87T, 87N, 87Q, 63 and monitoring that matches the transformer's value and criticality.
13. A setting philosophy for 87T and 87N together
Keentel's transformer protection settings follow a simple division of labor:
| Fault type | Primary electrical protection | Supplementary | Backup |
|---|---|---|---|
| Phase faults, high-current internal faults | 87T (restrained) and 87U (unrestrained) | 63 sudden pressure | 50/51 high side |
| Ground faults, delta winding and HV leads (grounded HV system) | 87T | 63 | High-side 50/51N, remote line ground protection |
| Ground faults, grounded-wye winding, resistance grounded | 87N | 63 | 51G on NGR |
| Ground faults, grounded-wye winding, solidly grounded | 87T (most of the winding) and 87N (near neutral) | 63 | 51N on neutral, high-side 50/51 |
| Turn-to-turn faults | 63 sudden pressure | 87Q, 87T for large turn counts | Gas accumulation, DGA |
| Incipient and core faults | Condition monitoring, gas accumulation | DGA, thermal | — |
These are starting points, not universal settings; every value is checked against the specific transformer, CTs, relay algorithm and system.
| Element | Parameter | Typical starting point |
|---|---|---|
| 87T | Minimum pickup | 0.3 pu (0.2 pu with good CTs and no LTC) |
| 87T | Slope 1 / Slope 2 | 25–35% / 50–80%, breakpoint 2–6 pu |
| 87T | Second-harmonic block | 12–15%, with cross-phase blocking for modern cores |
| 87T | Fifth-harmonic block | 35%, or per overexcitation study |
| 87U | Unrestrained pickup | 8–12 pu, above maximum inrush and below minimum internal heavy fault |
| 87N high-Z | Setting voltage | Above calculated stability voltage with ≥ 25–50% margin |
| 87N low-Z | Pickup | 10–20% of NGR current (LRG) or 5–10% of rated current (solid) |
| 51G on NGR | Pickup / curve | 10–20% of NGR; very or extremely inverse; coordinated with feeders |
The 87T and 87N elements are instantaneous unit protections and do not need time coordination with other elements; their security is achieved by restraint and by zone definition. The backup elements — 50/51 on the high side, 51G on the NGR, feeder ground elements — do. For BES transformers, NERC PRC-027-1 requires a documented process to develop, coordinate and periodically review protection system settings for BES elements, including coordination across ownership boundaries. Keentel's settings packages are structured to support that process: each setting has a basis, the coordination study shows margins, and the review interval and change triggers are documented.
Keentel Service Spotlight — Protection coordination study. Keentel's coordination studies for transformer substations include phase and ground time-current curves from the source line relays to the furthest downstream feeder device, the transformer through-fault damage curve per IEEE C57.109, the NGR thermal limit, and the unit-protection zones. The study documents margins and the PRC-027-1 review basis.
How Keentel Engineering helps here. Keentel develops new settings, peer-reviews settings developed by others, and resolves coordination conflicts between utilities, generator owners and large-load customers at the interconnection boundary.
14. Commissioning and site acceptance testing
A restricted ground fault scheme can be perfectly designed and perfectly set and still be wrong in the field, because its correctness depends on the relative polarity of four CTs that are installed in different places — three in the transformer or switchgear and one in the neutral lead or NGR enclosure. A reversed neutral CT produces no symptom during normal operation, because there is no neutral current. It reveals itself only when an external ground fault occurs and the element trips the transformer, or when an internal fault occurs and the element fails to operate. Commissioning must therefore prove polarity directly, not infer it.
1. CT tests: ratio, polarity, excitation curve, winding resistance and insulation resistance on every CT core, recorded against nameplate.
2. Wiring verification: point-to-point checks from CT terminals through test switches to relay inputs, including grounding of each CT circuit at one point only.
3. Relay settings verification: settings file loaded and compared with the approved settings; CT ratios, polarities and compensation settings checked against the CT data table.
4. Secondary injection: pickup, slope, harmonic blocking and timing for 87T; pickup and timing for 87N; directional supervision for low-impedance 87N; stability voltage and operating current for high-impedance 87N.
5. Primary injection or primary current tests: for 87N, inject primary current through a phase CT and out through the neutral CT to simulate an external ground fault (the element must restrain) and through the neutral CT alone to simulate an internal fault (the element must operate at the calculated primary current).
6. Trip checks: lockout relay, breaker trip coils, breaker failure initiation and SCADA alarms.
7. In-service load checks: after energization, record phase angles and magnitudes on all 87T inputs at load and confirm differential currents near zero; record any standing neutral current and the relay's restricted ground fault differential at load.
Step 5 is the step most often skipped, and it is the only step that proves the relative polarity of the neutral CT and the phase CTs. Where primary injection equipment cannot deliver enough current, Keentel uses a combination of single-CT primary polarity tests and calculated secondary injection that reproduces the exact relative polarity.
Keentel Service Spotlight — Commissioning and SAT witness. Keentel writes transformer protection test plans, witnesses factory and site acceptance tests, reviews test reports against the settings and drawings, and signs off energization readiness. Our companion guide on relay site acceptance testing for medium-voltage switchgear describes the full SAT process.
How Keentel Engineering helps here. Keentel's commissioning reviews focus on the failure modes that matter: CT polarity, CT ratio and tap selection, phase compensation, single-point grounding of CT circuits and lockout wiring. We document each with test evidence suitable for PRC-005-6.
15. Event analysis and misoperations
When 87T or 87N operates, or fails to operate, the event record from the numerical relay is the primary evidence. Keentel's analysis process for transformer protection events covers:
- Raw currents on every input — magnitude, angle and waveform, before and during the fault.
- Calculated quantities — differential and restraint per phase for 87T; neutral, residual and differential for 87N; harmonic content.
- CT behavior — signs of saturation, dc offset, remanence or a missing input.
- Sequence of events — element pickup and trip timing, lockout, breaker opening and current interruption.
- System context — fault location and type from line relays, digital fault recorders or PRC-028-1 recorders where available.
| Symptom | Common root cause |
|---|---|
| 87N trips on an external ground fault | Reversed neutral CT polarity; wrong neutral CT ratio setting; CT saturation with no directional supervision; open phase CT |
| 87N does not trip for an internal ground fault | Element not enabled; pickup set in wrong units; neutral CT shorted or bypassed; high-impedance scheme with an extra CT paralleled in |
| 87T trips on energization | Low second-harmonic ratio on a modern core; independent per-phase blocking; wrong compensation |
| 87T trips on an external fault | CT saturation on one side; slope too low; LTC range not considered; wrong phase compensation |
| 87T standing differential at load | Compensation error (Dyn1 vs Dyn11); CT phase rotation or polarity error; tap error |
For BES protection systems, a misoperation must be identified, analyzed and, where a cause is found, addressed through a corrective action plan under NERC PRC-004. Keentel's event analysis reports are written to support that process: they establish whether the operation was correct or a misoperation, identify the cause, and recommend corrective actions with a clear scope and verification step.
Keentel Service Spotlight — Event analysis. Keentel analyzes COMTRADE records from transformer relays, line relays and fault recorders, reconstructs the fault, recalculates the relay's response, and identifies the root cause. The deliverable includes corrective actions and the evidence package needed for PRC-004.
How Keentel Engineering helps here. Many transformer misoperations recur because the first investigation stopped at "relay operated, transformer tested good." Keentel's root-cause approach finds the wiring, setting or CT problem so the next external fault does not trip the transformer again.
16. NERC PRC-005-6 maintenance for transformer protection
For transformers that are part of the Bulk Electric System, PRC-005-6 applies to the protective relays that respond to electrical quantities, the communications systems that are part of the protection system, the voltage and current sensing devices that provide inputs to those relays, the station dc supply and the control circuitry associated with protective functions through the trip coils. Sudden pressure relays that trip are also addressed by PRC-005-6. The 87T, 87N, 51G and their CTs, trip paths and dc supply all fall within scope when the transformer is a BES element.
PRC-005-6 offers time-based, performance-based and condition-based maintenance programs, with minimum activities and maximum intervals listed in its tables for each component type. For a microprocessor relay with monitoring, the intervals are longer than for an electromechanical relay; for current sensing devices the requirement is to verify that the relays receive the expected current signals. The details and intervals must be taken from the current standard and the entity's documented program.
- The 87N element is easy to miss in a maintenance program because it is one of many elements in a multifunction relay. The program should list it explicitly.
- The neutral CT is a current sensing device in scope. It is often physically remote from the other CTs — in the NGR enclosure or on the neutral bushing — and must be included in the CT verification.
- Primary injection evidence from commissioning is the baseline for later verification. Keep it with the maintenance records.
- Any CT or wiring change — replacing an NGR, moving a neutral CT, changing a CT tap — requires re-verification of 87N polarity and sensitivity.
Keentel Service Spotlight — PRC-005-6 program support. Keentel builds and audits PRC-005-6 maintenance programs, writes component-level procedures for transformer protection (including 87N and sudden pressure relays), reviews test records for completeness and prepares audit evidence. Our NERC compliance services guide describes the full program.
How Keentel Engineering helps here. Keentel's PRC-005-6 gap assessments often find that the transformer differential is tested but the restricted ground fault element, the neutral CT and the 51G trip path are not explicitly listed. We close those gaps before an audit does.
17. Design checklist and the ten most common mistakes
- Is every grounded-wye winding identified, with its grounding method and maximum ground fault current?
- Has the 87T coverage of each grounded winding been calculated, as a percentage of the winding?
- Is 87N applied wherever 87T coverage is inadequate — and, on resistance-grounded windings, always?
- Are the 87N CT ratios, classes, knee points and winding resistances specified and suitable for the chosen scheme?
- Is the neutral CT located so that the NGR and its connections are inside or outside the zone as intended?
- Is the phase compensation setting taken from the transformer nameplate vector diagram?
- Is the 87T slope supported by an explicit error budget, including the LTC range?
- Is inrush security confirmed for the specific core design?
- Does the 51G on the NGR coordinate with feeders and protect the resistor within its rating?
- Is NGR monitoring provided?
- Are turn-to-turn faults covered by 63 and, where justified, 87Q?
- Does the commissioning plan include primary-current polarity proof for 87N?
- Are all elements, CTs and trip paths listed in the PRC-005-6 program where applicable?
1. Restricted ground fault available in the relay but never enabled or set.
2. Neutral CT polarity reversed and never tested with primary current.
3. Neutral CT ratio entered incorrectly in a low-impedance 87N element.
4. High-impedance scheme built with mismatched CT taps on multi-ratio CTs.
5. High-impedance stability voltage calculated with assumed, not measured, lead resistance.
6. No voltage limiter on a high-impedance scheme with high internal-fault voltage.
7. 87T compensation selected for the wrong vector group.
8. 87T minimum pickup lowered to "see" ground faults, at the cost of security, instead of adding 87N.
9. 51G on the NGR set slower than the resistor's 10 s rating allows at low currents, or not coordinated with feeders.
10. 87N, the neutral CT and the 51G omitted from the PRC-005-6 maintenance program.
How Keentel Engineering helps here. Keentel uses this checklist on every transformer protection design review, settings review and commissioning project. Owners receive a short report that marks each item as compliant, needing action or not applicable, with the evidence attached.
18. Putting it together: a complete protection package
This example pulls the guide together for the larger transformer of worked example 7: a 20/26.7/33.3 MVA, 69–13.8 kV delta–wye transformer with a ±10% load tap changer, 10% impedance on the 33.3 MVA base, and a 13.8 kV wye winding grounded through a 400 A, 10 s, 19.92 Ω NGR. The substation serves a mix of utility feeders and a large industrial customer.
Ratings and CTs
| Quantity | 69 kV winding | 13.8 kV winding | 13.8 kV neutral |
|---|---|---|---|
| Rated current at 33.3 MVA | 278.6 A | 1,393 A | 400 A (NGR, 10 s) |
| CT ratio | 300:5 (CTR 60), C800 | 2000:5 (CTR 400), C800 | 400:5 (CTR 80), C200 |
| 87T tap = 33,300 / (√3 × kV × CTR) | 4.644 A | 3.483 A | — |
The tap ratio is 4.644 / 3.483 = 1.33. Maximum through-fault current for a 13.8 kV bus fault, with an infinite 69 kV source, is 1,393 / 0.10 = 13.9 kA, or 34.8 A secondary on the 2000:5 CTs.
Coverage before 87N
From worked example 7, the 87T's maximum differential current for a 13.8 kV winding ground fault is about 0.17 pu of tap — below a 0.3 pu minimum pickup for every fault position. Without 87N, the only protection for a 13.8 kV winding ground fault is the 51G on the NGR and the sudden pressure relay.
Recommended settings (starting points)
| Element | Setting | Basis |
|---|---|---|
| 87T compensation | Per nameplate (ANSI delta–wye, LV lags 30°) | IEEE C57.12.00 connection; verified at load check |
| 87T minimum pickup | 0.30 pu | Above CT, LTC and magnetizing errors at light load |
| 87T slope 1 / slope 2 / breakpoint | 30% / 65% / 4 pu | Error budget with ±10% LTC (worked example 2); C800 CTs |
| 87T harmonic blocking | 2nd: 12% with cross-phase blocking; 5th: 35% | Modern core; overexcitation security |
| 87U | 10 pu | Above maximum inrush; well below heavy internal faults |
| 87N (low-impedance) | 60 A primary (15% of NGR), directional supervision enabled | Covers 85% of the 13.8 kV winding; secure for phase-CT saturation |
| 87Q (if available) | Per relay guidance, typically 0.1–0.3 pu with short delay | Turn-to-turn and unbalanced internal faults |
| 51G on NGR | 80 A pickup, IEEE very inverse, time dial set for ≥ 0.3 s coordination with feeder 51N | Coordination and NGR thermal protection (worked example 13 method) |
| NGR monitoring | Alarm on open resistor; 59N alarm/trip on sustained neutral voltage | Detects loss of grounding |
| 63 sudden pressure | Trip via lockout (with seal-in and appropriate supervision) | Turn-to-turn and arcing faults in oil |
If a high-impedance 87N were preferred
With dedicated 2000:5 C800 CTs on the phases and a matching 2000:5 neutral CT, a CT winding resistance of 0.8 Ω and a loop lead resistance of 0.4 Ω, the stability voltage would be 34.8 × (0.8 + 0.4) = 41.8 V; a setting of about 60–65 V would provide margin. But a 2000:5 neutral CT on a 400 A neutral gives only 1 A secondary at full NGR current, so the primary operating current — dominated by CT magnetizing currents multiplied by a CTR of 400 — would be a much larger fraction of the NGR current than in worked example 9. This is a common situation on larger transformers: when the phase CT ratio is large compared with the NGR current, a low-impedance scheme with a separate, smaller neutral CT usually gives better sensitivity.
What the package achieves
| Fault | Element that clears it | Approximate clearing |
|---|---|---|
| 13.8 kV winding ground fault, upper 85% of winding | 87N | 1–2 cycles + breaker |
| 13.8 kV winding ground fault, lowest 15% | 51G (time delayed), 63 if arcing in oil | Seconds |
| Phase-to-phase or three-phase internal fault | 87T / 87U | 1–2 cycles + breaker |
| 69 kV lead or bushing ground fault | 87T / 87U | 1–2 cycles + breaker |
| Turn-to-turn fault | 63, 87Q | Cycles |
| 13.8 kV feeder ground fault | Feeder 50/51N; 51G as backup | Feeder clearing time |
The residual risk is a low-level ground fault in the lowest 15% of the 13.8 kV winding, which relies on the 51G and the sudden pressure relay. Lowering the 87N pickup to 40 A would increase coverage to 90%, subject to confirming CT accuracy at 0.5 A secondary on the 400:5 neutral CT. Keentel documents that trade-off explicitly in the settings report so the owner can make an informed choice.
Fast clearing of ground faults has a safety dimension as well as an equipment one. In low-resistance grounded systems, ground fault current is limited, but an arcing ground fault inside switchgear or a transformer cable compartment can escalate to a phase-to-phase arc if it persists. Clearing the initial ground fault in cycles with 87N, rather than seconds with 51G, reduces the chance of escalation. Arc-flash studies to IEEE 1584 should use the actual protection clearing times, and Keentel's studies identify where enabling 87N or zone-selective schemes reduces the time that personnel are exposed to an escalating fault.
Keentel Service Spotlight — Integrated settings, coordination and arc-flash package. Keentel delivers transformer settings, the coordination study and the arc-flash study as one consistent package, so that clearing times, CT data and device settings match across all three — and so that the labels on the equipment reflect the protection actually in service.
How Keentel Engineering helps here. For each transformer, Keentel produces a one-page protection summary — like the table above — that shows which element clears which fault and how fast. Operations, maintenance and compliance staff can see at a glance what protects the asset and what depends on what.
Part C — Three Anonymous US Case Studies
The following case studies are anonymous composites drawn from the types of problems Keentel Engineering encounters in transformer protection work. Names, locations and some numerical details have been changed or combined; the engineering lessons are real.
Case study 1 — A data center transformer fault that only 87N saw
A hyperscale data center campus in the Mid-Atlantic region took service at 230 kV and distributed power at 13.8 kV to a set of 13.8–4.16 kV substations serving central plant chillers and large mechanical loads. Each 7.5 MVA, 13.8–4.16 kV delta–wye substation transformer had its 4.16 kV wye winding grounded through a 400 A, 10 s NGR. The transformers were protected by multifunction relays with 87T, 50/51 on both windings and 51G on the NGR. During a design review for a campus expansion, Keentel was engaged as owner's engineer to review the protection of the existing substations and to set the new ones.
Keentel's winding coverage analysis for the 7.5 MVA transformers produced the following:
| Quantity | Value |
|---|---|
| 4.16 kV rated current | 1,041 A |
| NGR current as a fraction of rated | 0.38 pu |
| Maximum 87T differential for a 4.16 kV winding ground fault | about 0.22 pu (fault at the terminal) |
| 87T minimum pickup as set | 0.30 pu |
| Portion of 4.16 kV winding covered by 87T | none |
The 87T could not detect a 4.16 kV winding ground fault anywhere in the winding. The only protection for such a fault was the 51G on the NGR, set at 60 A pickup on a very inverse curve that cleared a terminal fault in about 1.1 s and a fault 20% from the neutral (80 A) in roughly 30 s. The relays had a low-impedance restricted ground fault element available, and the 4.16 kV neutral CTs were installed, but the element had never been enabled.
Keentel prepared revised settings for all substations, enabling 87N with a pickup of 60 A primary (15% of NGR current), directional supervision, and the neutral and phase CT ratios verified against the as-built drawings. The coordination study was updated to confirm that the 51G still coordinated with the downstream motor and feeder ground elements and protected the NGR thermally. The commissioning plan for the existing substations, performed during scheduled maintenance windows on redundant equipment, included primary-current polarity tests of the neutral CTs. On one substation the neutral CT polarity was found reversed — a condition that would have caused a false 87N trip on the first external ground fault once the element was enabled. The wiring was corrected before the element was placed in service.
Fourteen months later, a 4.16 kV winding in one substation transformer developed an insulation failure to the core, roughly a quarter of the way up the winding from the neutral. The recorded neutral current was about 95 A. The 87T differential current was below 0.02 pu and the element did not pick up. The 87N element operated in about 30 ms, tripped the lockout relay and cleared the transformer. The redundant substation picked up the chiller load through the automatic transfer scheme without any interruption to IT load.
The post-event dissolved gas analysis and internal inspection confirmed a localized winding failure with limited collateral damage. Had the transformer remained energized until the 51G cleared — about 16 s at that current — the arc would have continued for more than 500 times longer, with far greater damage to the core and a real risk of tank rupture inside a building.
- An installed neutral CT and an available 87N element are not protection until the element is set, enabled and proven.
- The coverage calculation took less than an hour and changed the owner's risk profile completely.
- Primary-current polarity testing found a latent error that would have caused a misoperation.
- For a mission-critical facility, the value of fast clearing is measured in avoided damage and avoided downtime, not in relay hardware.
Keentel's role. Owner's engineer for the campus electrical system: protection review, winding coverage analysis, settings development, coordination study update, commissioning plan and witnessing, and event analysis.
Case study 2 — A solar main power transformer that tripped for someone else's fault
A 200 MW solar plant in the south-central United States connected to a 345 kV transmission system through a 345–34.5 kV main power transformer. The 345 kV winding was solidly grounded wye; the 34.5 kV winding was wye grounded through a 400 A NGR feeding the collector system, with a delta tertiary. The transformer's protection included 87T, a high-impedance restricted ground fault scheme on the 34.5 kV winding using dedicated CTs, and backup overcurrent elements.
Six months after commercial operation, the main power transformer tripped on the 34.5 kV 87N element during a ground fault on a 34.5 kV collector feeder. The feeder's own protection also operated. The plant lost all 200 MW of output and the owner faced both lost revenue and a NERC PRC-004 misoperation analysis. Keentel was engaged to analyze the event and correct the scheme.
The collector feeder fault was a cable termination failure close to the collector substation, with a ground fault current of about 390 A — essentially the full NGR current. That current should have circulated between the neutral CT and the faulted phase CT without producing a voltage across the 87N relay. The record showed a relay voltage peak well above the 87N setting for about three cycles, coinciding with the first cycles of the fault.
Keentel's review found three contributing problems:
1. Mismatched CT taps. The neutral CT and the 34.5 kV phase CTs were all 1200:5 multi-ratio CTs, as specified. The phase CTs were connected on the 1200:5 tap, but the neutral CT, supplied with the NGR by a different vendor, had been connected on its 600:5 tap to "improve sensitivity" during construction. In a high-impedance scheme this mismatch produces a differential current equal to half the neutral current for every external ground fault.
2. An underestimated stability voltage. The original stability calculation had used an assumed lead resistance. The actual neutral CT leads ran from the NGR enclosure, about 400 ft from the relay panel, which made the true loop resistance roughly four times the assumed value.
3. A setting chosen without margin. The relay setting voltage had been set at the theoretical minimum, with no margin for lead and CT resistance uncertainty.
The tap mismatch alone was enough to cause the trip; the other two problems meant that, even with the taps corrected, the scheme would have had too little margin against CT saturation during a nearby external phase-to-ground fault with significant dc offset.
- Reconnected the neutral CT on the 1200:5 tap, verified by ratio test, and locked the tap selection in the drawings.
- Measured the actual lead and CT winding resistances and the excitation curves of all four CTs.
- Recalculated the stability voltage with measured values and selected a new setting voltage with a 50% margin; confirmed that the CTs' excitation voltage exceeded twice the new setting.
- Recalculated the primary operating current (about 35 A, under 9% of the NGR current, giving about 91% winding coverage) and confirmed that the sensitivity remained acceptable.
- Added a voltage limiter sized for the internal-fault voltage and included its leakage current in the sensitivity calculation.
- Performed primary-current stability and operation tests and documented them for PRC-005-6.
- Prepared the PRC-004 analysis, identifying the misoperation cause and the corrective action plan with verification evidence.
- High-impedance restricted ground fault schemes are robust only when all CTs are identical in ratio and the stability calculation uses measured values.
- "Improving sensitivity" by changing one CT tap destroys the scheme's stability.
- On IBR plants, multiple vendors supply transformer, NGR and switchgear CTs; someone must own the CT data table across all of them.
- A transformer trip for an external collector fault turns a single-feeder event into a full-plant outage. Getting 87N right is a revenue issue as much as a protection issue.
Keentel's role. Event analysis, root cause, CT testing review, redesign of the high-impedance scheme, settings, commissioning test plan and witnessing, and PRC-004 corrective action documentation.
Case study 3 — A PRC-005-6 gap assessment at a 69 kV utility substation
A municipal utility in the Southeast owned several 69–13.8 kV substations with 20/26.7/33.3 MVA delta–wye transformers. The 13.8 kV wye windings were low-resistance grounded at 400 A. As a registered entity with BES-connected facilities, the utility asked Keentel to perform a PRC-005-6 gap assessment and mock audit of its protection system maintenance program, with a sample of substations selected for field verification.
The utility's maintenance program listed transformer differential relays, line relays and breaker trip coils, with intervals and procedures. It did not list the restricted ground fault elements or the NGR neutral CTs separately; the transformer protection was described simply as "87T relay." In the field, the transformers had numerical relays with 87T, 87N, 50/51 and 51G enabled — the 87N had been added during a relay upgrade program several years earlier.
Keentel's coverage analysis for these transformers (worked example 7 in Part B) showed that the 87N was the only fast protection for 13.8 kV winding ground faults: the 87T's maximum differential current for such a fault was about 0.17 pu against a 0.3 pu pickup. In other words, an element critical to protecting a valuable transformer was operating outside the documented maintenance program.
Field verification at the sampled substations included review of the most recent test records and limited testing during a planned outage. At one substation, Keentel's secondary injection and wiring review, followed by a primary-current polarity test, found the 13.8 kV neutral CT polarity reversed relative to the relay's convention. The 87N element was enabled. The substation had not experienced an external 13.8 kV ground fault large enough to trip the element since the relay upgrade, which is why the error had stayed hidden. The next feeder ground fault near the substation would very likely have tripped the transformer, interrupting customers on all feeders.
- Corrected the neutral CT polarity (by relay setting where the relay allowed, and by wiring correction where the utility preferred a physical fix), and re-tested with primary current.
- Revised the maintenance program to list the 87N element, the neutral CT, the NGR monitoring and the 51G trip path as explicit components with intervals and activities.
- Wrote a component-level test procedure for restricted ground fault elements, including primary-current polarity proof after any CT or wiring change.
- Reviewed the other substations' commissioning records and recommended polarity verification at two more sites where no primary-current test evidence existed.
- Prepared a mock audit report with findings, evidence and recommended actions, which the utility used to prepare for its scheduled compliance audit.
- A relay upgrade that adds protection functions must also update the maintenance program.
- The most valuable protection on a resistance-grounded transformer may be the element least likely to appear in the program documents.
- Polarity errors in restricted ground fault schemes are latent: they do not show up until the wrong fault occurs.
- A mock audit that combines document review with targeted field verification finds problems that document review alone cannot.
Keentel's role. PRC-005-6 gap assessment and mock audit, transformer protection coverage analysis, field verification and testing oversight, maintenance program and procedure revision, and audit preparation support.


















